HSJ POWER VENTER SPECIFICATIONS

Performance curves

Static pressure (inches H2O) vs CFM (std. air) at selected flue gas temps.

NOTE:  TO ARRIVE AT TOTAL SYSTEM STATIC PRESSURE REFER TO CURVE
AND ADD .38” TO COMPENSATE FOR VENT HOOD AND WIND RESISTANCE.

MOTOR ELECTRICAL DATA

Volts

115

Hertz

60

RPM

3000

Watts

95

Amps

1.26

Therm. Prot.

Yes

MOTOR MECHANICAL DATA

DESCRIPTION

Shaded Pole

Yes

Open

Yes

Int. Fan Cooled 

Yes

BEARINGS

Type

Sleeve

Material

Sintered Iron

UC1 UNIVERSAL CONTROL

Maximum Power Consumption 1/2 Amp @
120 VAC 50/60 Hz + Venter motor load

Pre-Purge: Options (0,15,30,60 seconds)

Post-Purge: Factory set at 2 minutes
Options (0,30 seconds; 1,2,4,8,16 minutes)

Dimensions: 5” x 8” (2’ electrical whip inc.)

SAFETY / INTERLOCK 

Fan Proving Switch 

5 VDC UC1 board supplied power switched
through Fan Prover.  UC1 burner / gas valve
interlock rated for 1 H.P. @ 120 VAC. 

MODELS AND APPLICATION:

HSJ (Gas or Oil) 

Used as a means of Side Wall Venting gas or
oil appliances which require a Post Purge cycle.
Used also to co-vent two gas heaters within
combined BTU/hr. input listed below (requires
accessory controls).  Includes a Fan Proving
Switch and the UC1 Universal Control for 24V,
115V or “dry contact” actuation.  LED diagnos-
tics and Pre / Post-purge options are standard
with the UC1.

HSUL-J (Discontinued 8/05)
HS115-J & HST-J (Discontinued 7/02)

Replace above models with HSJ.

Note:

Tjernlund Products, Inc. reserves the

right to make changes to specifications without
notification. 

ADJUSTMENT ROD

DAMPER

TOLERANCE: ±1/8" UNLESS OTHERWISE NOTED

SHADED POLE MOTOR

3,000 R.P.M.

ADJUSTABLE DAMPER

FAN PROVING PRESSURE SWITCH

4 5/8

3 1/8

9 5/8

4 I.D.

2

4 I.D.

7

9 7/8

1 7/8

1

4 3/4

7 5/8

4 I.D.

5 5/8

7 1/2

2 1/4

5 1/4

FIGURE 2061000-3

1 1/2

FAN PROVER SENSOR

SHIELD

DRIP

1 1/8

-SIDE VIEW-

-END VIEW-

-PLAN VIEW-

P/N 8506001 
REV. B 2/06

500°F

400°F

300°F

70°F

1.00

.80

.60

.20

.40

160

140

120

80

60

100

40

20

CFM (std air)

DIA.

VENT

BTU / HR

MAXIMUM PIPE LENGTH

OIL

GAS

23'

 -- 
 -- 

100'
100'

100'
100'
100'

35'

100'

100'

100'

125,000

100,000

75,000

50,000

4"

HSJ

500° F

400° F

300° F

FIRED

FIRED

AT STACK TEMPERATURE

(FT)

INPUT

PIPE

MODEL

TJERNLUND PRODUCTS, INC.

1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547