Parameter 3: Watt Meter Report Period
If the setting configured for 1 hour (set value = 720), the TZ69 will report its instant power consumtion every 1 hour to Z-Wave Controller. The maximum
interval to report its instand power consumption is 45 hours.
Size: 2 Byte, Default Value: 720
Setting
Description
1 - 32767
Time in 5 second steps
Parameter 4: KWH Meter Report Period
If the setting configured for 1 hour (set value = 6), the TZ69 will report its accumulated power consumtion every 1 hour to Z-Wave Controller. The maximum
interval to report its instand power consumption is 227,55 Days.
Size: 2 Byte, Default Value: 6
Setting
Description
1 - 32767
Time in 10 minutes steps
Parameter 5: Threshold of Watt for Load Caution
In the above form, when the value is 3000, if Relay 1 load by below 3000 watt turned into more than 3000 watt, will immediately send the instantaneous
load w value to Group 1.
Size: 2 Byte, Default Value: 3000
Setting
Description
10 - 3000
Threshold Watt
Parameter 6: Thresold of KWH for Load Caution
In the above form, when the value is 10000, if Relay 1 load by below 3000 watt, when the accumulation of Relay 1 consumed power more than 10000
KWH, will immediately send the accumulation of current consumed power to Group 1.
Size: 2 Byte, Default Value: 10000
Setting
Description
1 - 10000
Thresold in KWH