Vortex meters require a fully developed flow profile as a prerequisite for correct volume flow
measurement. Therefore, please note the following:
Orientation
Recommendation
Compact version
Remote version
A
Vertical orientation (liquids)
A0015591
1)
B
Horizontal orientation, transmitter head up
A0015589
2) 3)
C
Horizontal orientation, transmitter head down
A0015590
4) 5)
D
Horizontal orientation, transmitter head at side
A0015592
4)
1)
In the case of liquids, there should be upward flow in vertical pipes to avoid partial pipe filling (Fig. A).
Disruption in flow measurement!
2)
Danger of electronics overheating! If the fluid temperature is 侒 200
°
C (392
°
F), orientation B is not
permitted for the wafer version (Prowirl D) with nominal diameters of DN 100 (4") and DN 150 (6").
3)
In the case of hot media (e.g. steam or fluid temperature (TM) 侒 200
°
C (392
°
F): orientation C or D
4)
In the case of very cold media (e.g. liquid nitrogen): orientation B or D
5)
For "Wet steam detection/measurement" option: orientation C
Pressure measuring cell
Steam pressure measurement
Option
E
• With the
transmitter
installed at the
bottom or at the
side
• Protection
against rising
heat
• Reduction in
temperature to
almost ambient
temperature due
to siphon
1)
A0034057
㾎㾎
Orientation
The direction of the arrow on the sensor nameplate helps you to install the sensor according to the
flow direction (direction of medium flow through the piping).
F
A0034058
㾎㾎
1)
Note max. permitted ambient temperature of transmitter→ See page 35.