background image

 

 

172-65427MA-05  (JH7RH-P/JH7RHT-P)  29  Sep  2016 

1

 

Contents

 

Introduction .......................................................................... 1

 

Safety Considerations .......................................................... 2

 

Checking the Piping ............................................................. 4

 

Operation ............................................................................. 5

 

Specifications ....................................................................... 6

 

Configuration ....................................................................... 6

 

Installation............................................................................ 7

 

Maintenance ........................................................................ 8

 

Disassembly / Reassembly .................................................. 9

 

Instructions for Plug / Holder Disassembly and Reassembly  .. 13

 

Troubleshooting ................................................................. 14

 

Product Warranty ............................................................... 15

 

Options .............................................................................. 16

 

Introduction

 

 

Thank you for purchasing the 

  Free Float Steam Trap. 

This product has been thoroughly inspected before being shipped from the factory. 
When the product is delivered, before doing anything else, check the specifications 
and external appearance to make sure nothing is out of the ordinary. Also be sure to 
read this manual carefully before use and follow the instructions to be sure of using 
the product properly. 

This instruction manual is edited based on the JH-P Series (with cover plug). The 
JH-W Series (with socket welded cover connection), JH-F Series (with flanged cover 
connection) and JH-V Series (with manual air vent valve) are described at the end of 
this manual in the 'Option’ section.   

Both JH7RH-P and JH7RHT-P free float steam traps employ a hinge-less and lever-
less free float to rapidly, automatically and continuously discharge the inflowing 
condensate that is continuously generated inside the equipment, thus preventing the 
accumulation of condensate and thereby improving the heat transfer efficiency of the 
equipment. 
In particular, JH7RHT-P/JH7RHT-V (option) possess the highest heat resistance of 
the TLV steam trap product range, and are of a specification that is suitable for use on 
thermal power plant steam mains, which operate at increasingly high temperatures in 
recent years. 

This steam trap also employs a precision-ground float and three-point seating that 
supports the float securely at three points and ensures a high degree of sealing 
when even only minute quantities of condensate are present. 

This free float steam trap is suitable for locations at which extremely small amounts 
of condensate are generated, such as superheated and saturated steam mains and 
branches, and for applications under long continuous operation with the introduction 
of almost no air. 

If detailed instructions for special order specifications or options not contained in this 
manual are required, please contact 

  for full details. 

This instruction manual is intended for use with the model(s) listed on the front cover. 
It is necessary not only for installation but for subsequent maintenance, 
disassembly/reassembly and troubleshooting. Please keep it in a safe place for 
future reference. 

 

Summary of Contents for JH7RH-P

Page 1: ...ptember 2016 Free Float Steam Trap JH7RH P JH7RHT P Optional Models JH7RH W JH7RH F JH7RH V JH7RHT V Copyright 2016 by TLV CO LTD All rights reserved ISO 9001 ISO 14001 Manufacturer Kakogawa Japan is approved by LRQA LTD to ISO 9001 14001 ...

Page 2: ...ly discharge the inflowing condensate that is continuously generated inside the equipment thus preventing the accumulation of condensate and thereby improving the heat transfer efficiency of the equipment In particular JH7RHT P JH7RHT V option possess the highest heat resistance of the TLV steam trap product range and are of a specification that is suitable for use on thermal power plant steam mai...

Page 3: ...t of death or serious injury Indicates that there is a potential threat of death or serious injury Indicates that there is a possibility of injury or equipment product damage NEVER apply direct heat to the float The float may explode due to increased internal pressure causing accidents leading to serious injury or damage to property and equipment Install properly and DO NOT use this product outsid...

Page 4: ... recommended components when repairing the product and NEVER attempt to modify the product in any way Failure to observe these precautions may result in damage to the product and burns or other injury due to malfunction or the discharge of fluids Use only under conditions in which no freeze up will occur Freezing may damage the product leading to fluid discharge which may cause burns or other inju...

Page 5: ...ure has a check valve TLV CK been installed 5 Is a bypass valve installed 6 Is the inlet pipe as short as possible with as few bends as possible and installed so the liquid will flow naturally down into the trap 7 Has the piping work been done correctly as shown in the figures below Requirement Correct Incorrect Install catchpot with the proper diameter Diameter is too small Make sure the flow of ...

Page 6: ...ischarge of Large Quantities of Condensate Increases in the condensate inflow rate cause the condensate level in the trap to rise The float consequently rises and enlarges the opening of the orifice A allowing more condensate to be discharged In this manner continuous condensate discharge occurs while the opening size of the orifice varies depending on the condensate flow rate 3 Closed Position Wh...

Page 7: ...N Refer to the product nameplate for detailed specifications Maximum allowable pressure PMA and maximum allowable temperature TMA are PRESSURE SHELL DESIGN CONDITIONS NOT OPERATING CONDITIONS Valve No is displayed for products with options This item is omitted from the nameplate when there are no options Configuration Model Maximum Allowable Temperature TMA Maximum Allowable Pressure Maximum Opera...

Page 8: ...allation inspection maintenance repairs disassembly adjustment and valve opening closing should be carried out only by trained maintenance personnel 1 Before installation be sure to remove all protective seals 2 Before installing the product open the inlet valve and blow out the piping to remove any piping scraps dirt and oil Close the inlet valve after blowdown 3 Install the product so the arrow ...

Page 9: ...lting in faulty or low quality products or losses due to steam leakage Normal Condensate is discharged continuously together with flash steam and the sound of flow can be heard If there is very little condensate there is almost no sound of flow Blocked Discharge Impossible No condensate is discharged The trap is quiet and makes no noise and the surface temperature of the trap is low Blowing Live s...

Page 10: ...g procedures to remove components Use the same procedures in reverse to reassemble Installation inspection maintenance repairs disassembly adjustment and valve opening closing should be carried out only by trained maintenance personnel Detaching Reattaching the Cover Part During Disassembly During Reassembly Cover Nut Remove with a socket wrench Consult the table of tightening torques and tighten ...

Page 11: ...tighten to the proper torque see NOTE below Orifice Pull out from inside the trap body Fix with the orifice locknut see NOTE below Orifice Gasket Remove being careful not to scratch the orifice Replace with a new gasket clean the sealing surface on the orifice see NOTE below NOTE Special points pertaining to orifice and orifice gasket reassembly Follow the steps below when inserting the orifice in...

Page 12: ...m If drawings or other special documentation were supplied for the product any torque given there takes precedence over values shown here Special Notes 1 After operation following disassembly and reassembly it is recommended that the trap be let to sit for a day and then receive additional tightening 2 Using the tightening torques for the cover nuts and outlet cover nuts as a reference tighten unt...

Page 13: ...loded View Cover Plug Cover Plug Gasket Cover Nut Cover Cover Gasket Screen Screen Holder Float Cover Bolt Orifice Locknut Outlet Cover Gasket Outlet Cover Nut Snap Ring Screen Holder Retainer Orifice Orifice Gasket Outlet Cover Outlet Cover Bolt Body ...

Page 14: ...seize affixes the gasket tightly to the plug holder Check to make sure the gasket is not caught in the recesses of the threads 5 Hold the plug holder upside down to make sure that the anti seize makes the gasket stick to the plug holder even when the plug holder is held upside down 6 Screw the plug holder by hand into the product body while making sure that the gasket remains tightly affixed to th...

Page 15: ...et Compare specifications and actual operating conditions Steam locking has occurred Perform a bypass blowdown or close the trap inlet valve and allow the trap to cool Air binding has occurred Perform a bypass blowdown or consider switching to a product with a built in air vent or air vent valve Steam is discharged or leaks from the outlet blowing steam leakage Clogged orifice opening or rust and ...

Page 16: ... improper installation use handling etc by other than TLV CO LTD authorized service representatives 2 Malfunctions due to dirt scale rust etc 3 Malfunctions due to improper disassembly and reassembly or inadequate inspection and maintenance by other than TLV CO LTD authorized service representatives 4 Malfunctions due to disasters or forces of nature 5 Accidents or malfunctions due to any other ca...

Page 17: ...ver if low temperature condensate in the piping blocks the trap inlet passage displacement inside the piping of steam by condensate is obstructed and condensate can no longer flow into the trap steam locking Traps only function in the presence of condensate inflow A pressure balancing line prevents the occurrence of steam locking Install the pressure balancing line in the following manner Example ...

Page 18: ...o determine the condition of the fluid discharged General guidelines Cloudy water droplets and mist spraying out indicating that air and condensate are being discharged Clear indicating that steam is being discharged the valve port may now be closed The air vent valve stem cannot be removed from the air vent valve body Attempting to remove the valve stem by pulling it upward may damage it and caus...

Page 19: ...htly after operation Disassembly Reassembly of Air Vent Valve Air Vent Valve Unit Remove with a wrench Consult the table of tightening torques and tighten to the proper torque Air Vent Valve Gasket Remove the gasket and clean the sealing surface Replace with a new gasket coat surfaces with anti seize Table of Tightening Torques Part Name Torque Distance Across Flats N m lbf ft mm in Air Vent Valve...