<SET1 :
Input setting mode
>
SET1
INP
1.
Setting item selection screen
2.
Input type setting
Select input type
0
0
INP
3.
PV compensation gain setting
0.50
~
2.00
PVG
1
00
4.
PV compensation zero setting
-199
~
999
-199.9
~
999.9
PVS‘
0
5. PV
Filter setting
0.0
~
99.9
0
0
6.
Decimal point setting
0:
Not required
0.1
:
Required
(Except R/S/B Thermocouple)
DP
0
7.
Temperature unit setting
℃:
Celsius
℉:
Fahrenheit
C/F
*C
<
SET2 :
Key function setting mode
>
SET2
KEY
1.
Setting item selection screen
Setting related to
<SET3 :
Control setting mode
>
SET3
CNT
1.
Setting item selection screen
<SET4 : EV1
setting mode
>
SET4
AL1
Setting related to control
Setting related to input
key functions
<SET5 : EV2
setting mode
>
SET5
AL2
<SET6 :
Timer setting mode
>
SET6
TIME
<SET7 : LCD
setting mode
>
SET7
LCD
<SET0 :
Priority screen setting mode
>
SET0
PR1
Setting for priority screen
(Refer to Ex.1.)
M key
2.
Priority screen 1 setting
PRI1
OFF
Select 1st screen on
Run mode B
Select 2nd screen on
Select 3rd screen on
Select 4th screen on
Select 5th screen on
3.
Priority screen 2 setting
PRI2
OFF
4.
Priority screen 3 setting
PRI3
OFF
5.
Priority screen 4 setting
PRI4
OFF
6.
Priority screen 5 setting
PRI5
OFF
7.
Priority screen 6 setting
PRI6
OFF
8.
Priority screen 7 setting
PRI7
OFF
9.
Priority screen 8 setting
PRI8
OFF
10.
Priority screen 9 setting
PRI9
OFF
<
When select PID control
>
<
When select ON/OFF control
>
K
Thermocouple
J
R
T
N
S
00
01
02
03
04
05
B
Pt
100
JPt
100
06
10
11
●Setting mode
●POWER ON
●
RUN mode
A
.
Primary screen
Measured value
Set the temperature
required
Set value
(Press for 4 seconds)
▲KEY
▼KEY
▲KEY
▼KEY
●
Protect setting mode
Setting screen
Mode to set the protection level
“Input type setting screen” appears for 4seconds,
then it will oriceed to “Run mode” .
PTLV
0
Non-Protect
0
1
2
3
parameters except for the following:
Setting Change not possible.
PV compasation zero setting
Alarm reset
AT start/reset
Proportional band setting for OUT1/OUT2
Integral time setting
Deviative time setting
Control sensitivity setting for OUT1/OUT2
Upper limit setting for EV1/EV2
Lower limit setting for EV1/EV2
・
The Setting Mode Parameter blinds
・
Setting change for SV/Priority Screen is Possible
B
.
Priority screens (1
~
9)
Priority displays by setting
and shows max.9 screens by setting.
●
EX1
.
Priority screens & its setting
This function enables the selection of the most necessary screen indication
from all the screen indication found in the setting mode,and assign it to
eg
:
Basic screen
→
OUT1 manipulated value → Setting high limit for EV1
*
Screen is shifted when pressing M key each time.
the RUN mode on priority basis.
Please select priority screen indication through the priority screen setting mode.
●
EX2
.
Function
key works
This function is to enable F key to use as a specific key,for the following actions
selected in F key setting belonging to setting mode.
1. Digit shift
Setting digit shift is enabled when setting value is changed.
2. RUN/READY
Control stop(READY) and control performance(RUN) are
alternately switched by F key.
3. AT Start / Reset
AT(Auto -Tuning) starts instantly after pressing F key.
Start and Reset are alternately switched by F key.
4. Timer Start / Reset
Press once for function.
Press once for function.
5. Alarm Reset
6. Enter
Function
Effective
in all modes
Effective only
in Operating mode
●
EX3
.
To select PID
Features of type A,B,FUZZY
TypeA
If control is unstable under self-tuning,
please change to type A ,B or FUZZY and also ON/OFF control.
TypeB
FUZZY
the RUN mode on priority basis.
Basic PID
Over shoot protection PID
Effectively control the over shoot in the beginning of PID control.
●EX4. ARW (Anti-Reset-Windup)
ARW take effect for overshooting by over-integral of PID action.
・
ARW controls integral action (PV accords with SV).
・
If integral value goes down,it takes effects.
If integral value is set “0” ,it stops integral action.
Table1. To select input sensors and setting range. unit :
℃
Symbol
K Thermocouple
Low limit
~
High limit
-200 ~ 1372
0.0 Setting
J
-200 ~ 850
R
0 ~ 1700
T
-200 ~ 400
N
-200 ~ 1300
S
0 ~ 1700
B
0 ~ 1800
Pt100
-200 ~ 500
JPt100
-200 ~ 500
OPERATION FLOW AND SETTING MENU
*12*13
(Press for 2 seconds)
・
Setting change is possible with SV only.
・
The priority screen is with indication/
・
All setting mode parameters will be blinded.
・
SV is with indication / setting change not possible.
not possible.
・
Priority Screen is with indication / setting change
・
All setting mode parameters will be blinded.
Press for
2 seconds
Effective
in all modes
"
"
"
"
"
"
Select 6th screen on
Select 7th screen on
Select 8th display on
Select 9th screen on
M key
M key
M key
M key
M key
M key
M key
M key
M key , return to 1
M key , return to 1
M key
M key
M key
M key
M key
"
"
"
"
"
"
M key
M key
M key
M key
M key
seconds
times
-199.9 ~ 999.9
-199.9 ~ 850.0
-199.9 ~ 400.0
-199.9 ~ 999.9
-
-
-199.9 ~ 500.0
-199.9 ~ 500.0
-
*1
No indication when the type of control OUT1 is ON/OFF Control.
*2
No indication when the type of control OUT1 is PID Control.
*3
No indication when the OUT1 loop error determination time is “0” .
*4
No indication when the type of control OUT2 is either “None” or “EV2” .
*5
No indication when the type of control OUT2 is ON/OFF Control.
*6
No indication when the type of control OUT2 is PID Control.
*7
No indication when the OUT2 loop error determination time is “0” .
*8
No indication when the EV1 Function is set at “No Function” .
*9
No indication when the EV1 Function is not used in the Upper Limit Alarm.
*10
No indication when the EV1 Function is not used in the Lower Limit Alarm.
*11
No indication when the EV1 & 2 Functions to “No Function” .
*14
No indication when EV2 Function is set at “No Function” .
*15
No indication when the EV2 Function is not used in the Upper Limit Alarm.
*16
No indication when the EV2 Function is not used in the Lower Limit Alarm.
*17
No indication when the EV 1 & 2 Functions to “No Function” .
*12
No indication when Option-B is not specified.
*13
No indication when the type of Control OUT2 is set to anything other than “EV2” .
*18
No indication when the Timer Output is set to “Timer Not Used” .
*19
No indication when the Timer Function is set to other than “SV Start” .
2.
Function key function setting
FU
00++
①
Function setting
0
:
None
1
:
Digit shift
2
:
RUN/READY
3
:
AT start/stop
4
:
Timer start/stop
5
:
Alarm reset
6
:
E
NTER
②
Pressing time setting
0
:
None
1
:
Pressing time 1 second
2
:
Pressing time 2 seconds
3
:
Pressing time 3 seconds
4
:
Pressing time 4 seconds
5
:
Pressing time 5 seconds
3.
Key-lock setting
0
LOC
Lock OFF
Lock all
Lock run mode
Lock except run mode
※
Protect Level Setting is not subjected to
Key-Lock Setting.
0
‘
1
‘
2
‘
3
4.
Alarm reset
0
0
ALRS
No alarm occurrence
Only EV1 is occurring
Only EV2 is occurring
0
0
0
1
1
0
1
1
Both EV1/EV2 are occurring
Screen for Alarm reset of EV1/EV2
※
Press F key for 1 second to reset the alarm.
(The indication momentarily disappears as
the Alarm reset is executed).
2.
SV limiter upper limit
SLH‘
1200
3.
SV limiter lower limit
SLL‘
0
4.
Control mode setting
RUM
MD
Control start
Control stop
Manual
RUN
RDY
MAN
Setting for control mode
5.
Control type setting
CNT
‘
020++
①
Function
0
:
TypeA
1
:
TypeB
2
:
Fuzzy
③
Control type of OUT2
0
:
None
1
:
PID control
2
:
ON/OFF control
3
:
EV2 output
②
Coutrol type of OUT1
1
:
PID control
2
:
ON/OFF control
①
②
③
②
①
※
When Option B is not specified,Control type of
OUT2 shall be fixed at “None” .
6.
Forward/reverse operation setting
0
:
Reverse operation
DIR‘
0
1
:
Forward operation
7.
Operating amount for OUT1
MV1‘
0
0
M key
M key
8.
Tuning type setting
1
TUN
*1
Auto-tuning
Self -tuning
Auto-tuning
Self -tuning
Auto-tuning
1
2
3
4
5
:
OUT
1
: OUT1
: OUT2
: OUT2
: OUT1/OUT2
9.
AT coefficient setting
ATG
1
0
10.
AT sensitivity setting
ATC
2
11.
AT start/stop
AT
OFF
AT stop
AT start
※AT
start and ATstop are alternately switched
OFF
ON
12.
Proportional band setting for OUT1
P1
3
0
13.
Integral time setting
I
0
14.
Deviative time setting
D
0
15.
Proportional cycle setting for OUT1
T1
20
16.
ARW setting (see Ex.4)
ARW
11
0
0
17.
Operating amout limiter upper limit for OUT1
MLH1
10
0
0
18.
Operating amout limiter lower limit for OUT1
MLL1
0
0
19.
Sensitivity setting for OUT1
C1
1
21.
Loop anormaly time setting for OUT1
LOP1
0
seconds
22.
Loop anormaly PV change threshold for OUT1
PS1
0
23.
Loop anormaly PV threshold for OUT1
TS1
0
24.
Protection OFF timer time setting for OUT1
FDT1
0
25.
Protection ON timer time setting for OUT1
NDT1
0
26.
Operating amount for OUT2
Displays operating amount for OUT2
and set the amount on manual control.
MV2‘
0
0
0.0
~
100.0(
%
)
MLL2
~
MLH2
(%)
27.
Proportional band setting for OUT2
0
.
10~10
.
00
P2
1
00
28.
Proportional cycle setting for OUT2
T2
20
29.
Operating amout limiter upper limit for OUT2
MLH2
10
0
0
MLL2
~
100.0
%
30.
Operating amout limiter lower limit for OUT2
MLL2
0
0
0.0
~
MLH2
%
20.
OFF point position setting for OUT1
CP1
0
*1
*2
*3
*3
*2
*2
*4
*4 *5
*4 *5
*4 *5
*4 *5
*1
*1
*1
*1
*1
*1
*1
*1
*1
*2
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M
key
(
Go to 21
)
31.
Sensitivity setting for OUT2
C2
1
32.
OFF point position setting for OUT2
CP2
0
*4 *6
*4 *6
33.
Loop anormaly time setting for OUT2
LOP2
0
※
At “0” setting,there is no loop error determination.
34.
Loop anormaly PV change threshold for OUT2
PS2
0
35.
Loop anormaly PV threshold for OUT2
TS2
0
36.
Protection OFF timer time setting for OUT2
FDT2
0
37.
Protection ON timer time setting for OUT2
NDT2
0
*4 *7
*4
38.
Balance less / Bump less
BMP
1
No Balance less / Bump less function
With Balance less / Bump less function
0
1
39.
Manual reset setting
PBB
0
0
0.0
~
100.0%
-100.0
~
100.0%
(
Heat / Cool
)
*1
40.
Dead band setting
DB
0
-100
~
100
*4
41.
Ramp time setting
RMP
0
0
※
Ramp function OFF at 0.0
42.
Control back up function setting
PWZ
0
0
0.0
~
10.0
*4 *7
*6 *4
2.
EV1 setting mode
EV1 alarm function 1 setting
A1F1
000++
①
Function
0
:
None
1
:
Deviation upper and lower limits
2
:
Deviation upper limit
3
:
Deviation lower limit
4
:
Deviation range
5
:
Absolute value upper and lower limits
6
:
Absolute value upper limit
7
:
Absolute value lower limit
8
:
Absolute value range
③
②
①
③
Control mode interlocking function
②
Add-on function
0
:
None
1
:
Hold
2
:
Standby
3
:
Delay
4
:
Hold
+
Standby
5
:
Hold
+
Delay
6
:
Standby
+
delay
7
: Hold
+
standby
+
delay
3.
EV1 alarm upper limit setting
A1H
0
-1999
~
3276
or
-199.9
~
999.9
※
In case of thermocouple R/S/B : -1999
~
3276
4.
EV1 alarm lower limit setting
A1L
0
5.
EV1 alarm sensitivity setting
A1C
0
0
~
999 or 0.0
~
999.9
6.
EV1 alarm delay timer setting
A1T
0
0
〜
9999
seconds
7.
EV1 alarm function 2 setting
EV1 alarm function 2 setting
for PV error
A1F2
000++
①
Function
0
:
None
1
:
PV error
③
②
①
②
Add-on function
0
:
None
1
:
Hold
2
:
Delay
3
:
Hold
+
Delay
8.
EV1 alarm function 3 setting
EV1 alarm function 3 setting
A1F3
00++
①
Function
0
:
None
1
:
Loop error
②
①
②
Add-on function
0
:
None
1
:
Hold
for loop anormaly
9.
EV1 alarm polarity setting
A1P
0
Normal open
Normal close
0
1
*8 *9
*8 *10
*8
*11
*12*14
*15
*12*14
*12*14
*12*17
*12
*12
*12
*16
0
:
All modes
1
:
RUN/ MANUAL mode only
2
:
RUN mode only
*12
M key
M key
M key
M key
M key
2.
Timer output setting
0
TMO
Non-use timer function
Control
EV1 output
EV2 output
※
“3” is not selectable when Option-B is not specified.
0
‘
1
‘
2
‘
3
3.
Function setting
1
TMF
Auto start
Manual start
EV1 start
Auto start
Manual start
1
2
3
4
5
EV1 start
SV start
EV2 start
6
7
8
EV2 start
9
( ON delay
)
( ON delay
)
※
“8” and “9” are not selectable
when Option-B is not specified.
4.
Unit setting
H/M
1
Hour / Minute
Minute / second
1
2
5.
Start SV permissible range setting
TSV
0
6.
Time setting
TIM
00
:
00
~
99
:
59
(
Hour/Minute
)
00
:
00
~
99
:
59
(
Minute/second)
)
7.
Remaining time monitor
TIA
00 00
Screen for remaining time monitor
2.
Brightness setting
LLV
100
5
~
100
%
3.
Dimming function setting
LRFT
0
0
~
9999
seconds
※
No dimming function when set to “0” .
4.
Dimming Brightness setting
LRLV
5
0
~
100
%
:
00 00
:
*18
*18*19
*18
*18
*18
M key
M key
M key
M key
M key , return to 1
M key
M key
0.1
~
10.0
times
% per
SLL
〜
SLH
seconds
1
〜
120
%
0.0
~
110.0
%
MLL1
~
100.0
%
0.0
~
MLH1
Setting range :
Setting unit :
Setting range :
Setting unit :
Setting range :
Setting unit :
0.1
~
200.0
seconds
0
~
3600
Setting range :
Setting unit :
Setting range :
Setting unit :
Setting range :
Setting unit :
Setting range :
Setting unit :
Setting range :
Setting unit :
Setting range :
Setting unit :
Setting range :
Setting unit :
Setting range :
Setting unit :
*6 *4
1.
Setting item selection screen
Start and Reset are alternately switched by F key.
Digit under selection will blink.
M key , return to 1
M key
M key
Setting range :
Setting range :
Setting unit :
Setting unit :
Setting range :
Setting unit :
by F key.
0
〜
999 or 0.0
〜
999.9
Setting range :
Setting unit :
-199
~
999 or -199.9
~
999.9
Setting range :
Setting unit :
0
~
9999
seconds
Setting range :
Setting unit :
Setting range :
Setting unit :
Setting range :
Setting unit :
※
At “0” setting,there is no loop error
PV change determination.
Setting range :
Setting unit :
Setting range :
Setting unit :
※
At “0” setting,there is no loop error determination.
Setting range:
Setting unit :
seconds
Display amount :
Setting amount :
Setting range :
Setting unit :
Low to high limit
※
Keep the difference of more than 5 degrees(
℃ or ℉)
Setting range :
Setting unit :
Low to high limit
between Low
and high limit of the SV limiter.
※
At “0” setting,there is no loop error
PV threshold determination.
※
At “0” setting,there is no loop error
PV change determination.
※
At “0” setting,there is no loop error
PV threshold determination.
Setting range :
Setting unit :
Setting range :
Setting unit :
0
~
99
Minuites
Setting range :
Setting unit :
0
~
99
Minuites
Setting range :
Setting unit :
Setting range :
Setting range :
-100.0
~
100.0
℃
or
℉
Setting unit :
℃
/min. or
℉
/min.
Setting range :
Setting unit :
※
Control back up function OFF at 0.0
Setting range :
Setting unit :
℃
or
℉
℃
or
℉
℃
or
℉
℃
or
℉
℃
or
℉
℃
or
℉
℃
or
℉
℃
or
℉
℃
or
℉
℃
or
℉
℃
or
℉
℃
or
℉
℃
or
℉
1.
Setting item selection screen
Setting range:
Setting unit :
℃
or
℉
-1999
~
3276
or
-199.9
~
999.9
※
In case of thermocouple R/S/B : -1999
~
3276
Setting range:
Setting unit :
℃
or
℉
Setting range:
Setting unit :
℃
or
℉
Setting range :
Setting unit :
M key
M key
M key
③
Control mode interlocking function
0
:
All modes
1
:
RUN/ MANUAL mode only
2
:
RUN mode only
M key , return to 1
M key , return to 1
2.
EV2 setting mode
EV2 alarm function 1 setting
A2F1
000++
①
Function
0
:
None
1
:
Deviation upper and lower limits
2
:
Deviation upper limit
3
:
Deviation lower limit
4
:
Deviation range
5
:
Absolute value upper and lower limits
6
:
Absolute value upper limit
7
:
Absolute value lower limit
8
:
Absolute value range
③
②
①
③
Control mode interlocking function
②
Add-on function
0
:
None
1
:
Hold
2
:
Standby
3
:
Delay
4
:
Hold
+
Standby
5
:
Hold
+
Delay
6
:
Standby
+
delay
7
: Hold
+
standby
+
delay
3.
EV2 alarm upper limit setting
A2H
0
-1999
~
3276
or
-199.9
~
999.9
※
In case of thermocouple R/S/B : -1999
~
3276
4.
EV2 alarm lower limit setting
A2L
0
5.
EV2 alarm sensitivity setting
A2C
0
0
~
999 or 0.0
~
999.9
6.
EV2 alarm delay timer setting
A2T
0
0
〜
9999
seconds
7.
EV2 alarm function 2 setting
EV2 alarm function 2 setting
for PV error
A2F2
000++
①
Function
0
:
None
1
:
PV error
③
②
①
②
Add-on function
0
:
None
1
:
Hold
2
:
Delay
3
:
Hold
+
Delay
8.
EV2 alarm function 3 setting
EV2 alarm function 3 setting
A2F3
00++
①
Function
0
:
None
1
:
Loop error
②
①
②
Add-on function
0
:
None
1
:
Hold
for loop anormaly
9.
EV2 alarm polarity setting
A2P
0
Normal open
Normal close
0
1
0
:
All modes
1
:
RUN/ MANUAL mode only
2
:
RUN mode onl
M key
M key
M key
M key
M key
Setting range:
Setting unit :
℃
or
℉
-1999
~
3276
or
-199.9
~
999.9
※
In case of thermocouple R/S/B : -1999
~
3276
Setting range:
Setting unit :
℃
or
℉
Setting range:
Setting unit :
℃
or
℉
Setting range :
Setting unit :
M key
M key
M key
③
Control mode interlocking function
0
:
All modes
1
:
RUN/ MANUAL mode only
2
:
RUN mode only
M key , return to 1
1.
Setting item selection screen
EV2 output function setting
1.
Setting item selection screen
Setting concerned with
timer parameters
EV1 output function setting
1.
Setting item selection screen
Setting related to LCD
Setting range :
Setting unit :
Setting range :
Setting unit :
Setting range :
Setting unit :
M key
M key
M key
M key , return to 1
( ON delay
)
( OFF delay
)
( OFF delay
)
( OFF delay
)
( OFF delay
)
( ON delay
)
( OFF delay
)
0
~
999 or 0.0
~
999.9
Setting range:
Setting unit :
℃
or
℉
Setting range:
0
〜
999 or 0.0
〜
999.9
0
〜
999 or 0.0
〜
999.9
0
〜
999 or 0.0
〜
999.9
0
〜
999 or 0.0
〜
999.9
0
〜
999 or 0.0
〜
999.9
-199
~
999 or -199.9
~
999.9
0
~
9999
0.0
〜
999.9
0
〜
999 or 0.0
〜
999.9
Setting range:
Setting unit :
0
~
3600
1
〜
120
Setting range :
Setting unit :
seconds
Setting range :
Setting unit :
Setting range :
Setting unit :
M key (
Go to 33
)
M key
M key
M key
※Timer
start and stop are alternately
switched by F key.
0
~
99
Minuites
0
~
99
Minuites
~~~~
Displays whenever input value exceeds the high limit of display range.
Also displays when the wire is snapped off thermocouple and that of R.T.D.
____
Displays whenever input value exceeds the low limit of display range.
ERR0cv
Displays at memory error.
ERR1cv
Displays at input circuit error.
ERR2cv
Displays when auto-tuning does not end after 3 hrs.,
or when error occurs during the auto-tuning.
Displays when the parameter change is attempted during key lock mode.
LOC
Displays when the control mode change is attempted
FUNC
during which function keys are allocated to RUN/READY.
Displays during auto-tuning.
AT
Displays when the control mode change is attempted
TIME
Other Display Indication
during which the timer is in use..
TOHO ELECTRONICS INC.
2-4-3 NISHIHASHIMOTO MIDORI-KU SAGAMIHARA KANAGAWA
252-0131 JAPAN
Phone: +81-50-3535-9960 Fax: +81-42-700-2118
overseas@toho-inc.co.jp
http://www.toho-inc.com
Head office:
E-Mail:
URL:
▲KEY
▼KEY
▲KEY
▼KEY
▲KEY
▼KEY
▲KEY
▼KEY
▲KEY
▼KEY
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
Run mode B
Run mode B
Run mode B
Run mode B
Run mode B
Run mode B
Run mode B
Run mode B
Magnification to
MV1
Displays operating amount for OUT1
and set the amount on manual control.
0.0
~
100.0(
%
)
MLL1
~
MLH1
(%)
Display amount :
Setting amount :
※
Keep the difference of more than 5 degrees(
℃ or ℉)
between Low
and high limit of the SV limiter.
M key
<
When select PID control
>
<
When select ON/OFF control
>
Blind setting mode
****
ON
Value is indicated.
No indication
ON
OFF
**** :
Selected parameter is indicated.
M key (
Press for 10 seconds)
Indication disappears momentarily
SET0
ON
SET1
ON
▲
▼
SET2
ON
▲
▼
SET3
ON\
▲
▼
SET4
ON
▲
▼
SET5
ON
▲
▼
SET6
ON
▲
▼
▲
▼
SET7
ON
PRI1
ON
INP
ON
FU
ON
SLH
ON\
A1F1
ON
A2F1
ON
TMO
ON
LLV
ON
▲
▼
M key
M key
M key
M key
M key
M key
M key
M key
to
SET0
M key (
Press for 2 seconds)
Reset the power for Blind setting mode OFF.
Shift to Blind setting mode
※
ON/OFF is changed by F key.
●POWER ON
“Input type setting screen” appears for 4 seconds,
then it will procceed to “Run mode” .
●RUN mode
F
key (
Press for once)
M
key (
Press for once)
●RUN mode
Please select parameters to be blinded
through the Blind setting mode.