7(12)
2 Assembly Instructions
2.1 General:
The product must be installed by a person who has the professional knowledge required
to perform the installation correctly. Unless the installation is performed by a professional,
the insurance companies may claim that the insurance does not cover any damage that
has occurred and that the offers made by the insurance companies to the property owner
are invalid.
If the ball valves are open for more than 72 hours, the ball valve is exercised automatically,
but the water is not completely turned off.
With a water switch, a washing machine can also be placed in the kitchen without a
floor drain, if there is a waterproof surface and a water sensor is placed so that any
water leaking from the equipment can be detected so that the leak can be automatically
stopped. (According to Safe Water Installation 2016: 1 Section 3.6.3)
This of course also applies to other pressurised equipment such as dishwashers, coffee
machines, and refrigerators / freezers with automatic water supply. If a water-connected
appliance other than a dishwasher or washing machine is connected, the installation must
be supplemented with a non-return valve, according to Safe Water Installation 2016:1
Section 4.3.4.
2.2 Installation:
Motorised Ball Valves: (art. no. 2130051)
The unit is intended for tap water, 0-60 ° C and 0-10 bar.
Fitted on the cold and hot water pipes. They can be mounted
horizontally, vertically, or upside down and independent of
flow direction. The unit has an internal R-thread. Connect to
them to pipes, for example with compression fitting according to the pipe and coupling
manufacturer's instructions. Use the required sealant. The unit must not be mounted in a
concealed place; it must be placed so that it can be changed and so that any leaking water
can be easily detected. The units must be installed in a room with a waterproof floor, in a
distribution cabinet, or in a custom space. If a distribution cabinet is used, the installation
instructions for this must be followed.
After mounting, the installation must be checked for leaks with the tap water installation's
existing water pressure according to the instructions on www.säkervatten.se.
(Up to three parallel motorised ball valves can be installed. Additional valves are ordered
separately)