Battery and Charger
MERGE 11-25
Chapter 11
a problem with the battery pack (voltage not attaining the required level), or that the
charger output was reduced due to high ambient temperatures.
[4 FLASH] Check Battery: the battery pack could not be trickle charged up to the minimum level
required for the charge to be started. This may indicate that one or more cells in the
battery pack are shorted or damaged.
[5 FLASH] Over-Temperature: auto-recover. Charger has shutdown due to high internal
temperature which typically indicates there is not sufficient airflow for cooling-see
installation instructions 1). Charger will restart and charge to completion if
temperature comes within accepted limits.
[6 FLASH] QuiQ Fault: an internal fault has been detected. If fault 6 is again displayed after
interrupting AC power for at least 15 seconds, the charger must be brought to a
qualified service depot.
Maintenance instructions
1. For flooded lead-acid batteries, regularly check water levels of each battery cell after charging
and add distilled water as required to level specified by battery manufacturer. Follow the
maintenance and safety instructions recommended by the battery manufacturer.
2. Make sure charger connections to battery terminals are tight and clean.
3. Do not expose charger to oil, dirt, mud or to direct heavy water spraying when cleaning vehicle.
Specifications
DC Output-see Operating Instructions
QuiQ Model:912-
48xx
Voltage-nom(v) 48
Voltage-max(v) 67.2
Current-max(A) 18
Battery Type
Specific to selected algorithm
Reverse Polarity
Electronic protection-auto-reset
Short Circuit
Electronic current limit
Ac input
All models
Voltage-max(Vrms) 85—265
Frequency(Hz) 45—65
Current-max(Arms) 12A
@ 104VAC(reduced 20%<104)
Current-nominal(Arms)
10A @ 120VAC/5A @ 230VAC
AC Power Factor
>0.98 at nominal input current