background image

Guidance MP-888 - Supplement to the manual of instructions 

10/10 

 

 

P43 

Hysteresis cooling 

Setting depends 
on model 

(0.2...25.0°C) 
(0.4...45.0°F) 

      Period between ON and OFF of cooling. 

This value has to be adjusted correctly 
according to the controller adjustment 
tables for temperature control units and 
chillers. 

P44 

Differential portion 
heating and cooling, 
controller parameter 

Setting depends 
on model 

(0...100%) 

      Differential portion of the PID control. 

Controls the max. speed of the 
controller 

P45 

Relation between 
cooling- and heating 
capacity 

(1...50) 

      Adjusting of the cooling capacity 

0: 

2-point cooling (Standard) 

1:   cooling = heating capacity 
50:  cooling > heating capacity 

P47 

Minimal switching 
time cooling,  
controller parameter 

1s 

(0.5...9s) 

      Minimal switching time for cooling relay. 

Only active if P45 is higher than 0 

P48 

Minimal switching 
time heating,  
controller parameter 

2s 

(1...9s) 

      Minimal switching time for heating relay. 

If P45 = 0, so also relevant for the 
cooling relay 

P49 

Cycle time,  
controller parameter 

15s 

(6...255s) 

      Controller time base of PWM-outputs 

Time of the analyse of the control 
system to define the variable  

P53 

Flow unit 

0: Flow OFF 
1: Impulse (Hz) 
2: litres/min 
3: US gallons/min 
4: Imperial gal./min 

      Flow unit to display 

1 US gallon  

= 3.785 litres 

1 Imperial gallon   = 4.546 litres 

P60 

Flow measurement 

Calibration table 

0 = Manual 
1 = Small units 1 
2 = Medium units 
3 = Large units 
4 = Reserved 
5 = Small units 2 
6 = Reserve 

      Selection of the calibration table for flow 

measurement 

P61 

Flow measurement 
point 1 

x Hz

 

y l/min

 

      Relevant calibration curve for flow 

measurement depending on P60 

P62 

Flow measurement 
point 2 

x Hz

 

y l/min

 

      Relevant calibration curve for flow 

measurement depending on P60 

P63 

Flow measurement 
point 3 

x Hz

 

y l/min

 

      Relevant calibration curve for flow 

measurement depending on P60 

P64 

Flow measurement 
point 4 

x Hz

 

y l/min

 

      Relevant calibration curve for flow 

measurement depending on P60 

P65 

Flow measurement 
point 5 

x Hz

 

y l/min

 

      Relevant calibration curve for flow 

measurement depending on P60 

P66 

Lower alarm limit 
(P61) 

30% 

      Only valid for automatic node (P3=1) to 

calculate the alarm point 

P67 

Upper alarm limit 
(P65) 

10% 

      Only valid for automatic mode (P3=1) to 

calculate the alarm point 

 

Summary of Contents for MP-888

Page 1: ...Guidance Supplement to the manual of instructions Microprocessor Temperature Controller MP 888 software version C30 06 2014 Version 14...

Page 2: ...binding obligation on the part of TOOL TEMP AG and are subject to change without notice In case of inconsistencies in the English translation the German version shall prevail Copyright 2013 TOOL TEMP...

Page 3: ...control active LED green Alarm flow control LED red 8 LED Cooling Lights up when the cooling relay is activated 9 LED Heating Lights up when the heating relay is activated 10 LED Sensor failure Light...

Page 4: ...ensor connection 21 23 Temperature sensor note 22 Pt 100 compensation 5 Flow control encoder signal 6 Connection external set point 26 28 Analog input 4 20mA 27 28 Analog input 0 10 V 7 Connection act...

Page 5: ...T 280 2 P 46 P US 46 TT 360 TT 370 TT 380 TT 380 2 TT 380 48 kW P 47 P US 47 TT 300 TT 301 TT 302 TT 303 TT 304 TT 305 TT 500 TT 700 Temperature Control Units with flow control Programme New models Ol...

Page 6: ...0 WK TT 216 000 OT TT 14 000 E LC TT 4 500 TT 5 000 TT 9 500 TT 11 000 TT 11 000 WK TT 12 000 TT 12 000 WK TT 14 000 TT 14 000 WK TT 20 000 TT 23 000 TT 23 000 WK TT 25 000 TT 28 000 TT 28 000 WK TT 2...

Page 7: ...ress button once to save 4 Navigation in the controller Enter into the controller and navigate to the different parameter To enter into the programme of the controller the program button has to be pre...

Page 8: ...1 Automatic If the automatic flow measurement is enabled after 20s the measured flow is stored and monitoring is enabled The green LED lights up P4 Alarm value flow 8 0 L 0 1 999 9 L P3 set to manual...

Page 9: ...ature at 0 V OUTPUT 0 0 C 32 0 F 50 0 399 9 C 58 0 751 8 F Lower scaling point of the voltage analog output 0 V corresponds to 0 C P32 Temperature at 10 V OUTPUT 400 0 C 752 F 49 9 400 0 C 57 8 752 0...

Page 10: ...15s 6 255s Controller time base of PWM outputs Time of the analyse of the control system to define the variable P53 Flow unit 0 Flow OFF 1 Impulse Hz 2 litres min 3 US gallons min 4 Imperial gal min F...

Reviews: