35
ADDITIONAL INFORMATION
This chapter contains additional information about components
that are not visible on the outside of the ECO-ClimaTEC but are
responsible for securing the ECO-ClimaTEC itselves.
This chapter gives you some inside information for reference.
TEMPERATURE LIMITER
The temperature limiters are mounted on top of the TCT-units.
These limiters will shut the system down when the unit has
reached a temperature of ca. 50°C. This temperature is reached
when the liquid flow inside the TCT-unit has a temperature of ca.
65°C. The limiter avoids that the components in the ECO-ClimaTEC
get damaged by overheating. The system will restart when the
outer surface of the TCT-unit has cooled down to a temperature of
approximately 35°C. At room temperature this takes about 20 min.
LEVEL SWITCH
The level switch checks the liquid level inside the reservoirs. If the
level of the liquid gets below a certain level, the level switch will
shut the system down. This problem can be solved by refilling the
reservoir. This refilling can be done by removing the lid of the ECO-
ClimaTEC and the plugs on top of the reservoirs. After removing the
plugs, the cooling fluid can be poured into the reservoir until the
level of the fluid is on an equal height as the starting plane of the
screw thread of the plug.
It is recommended to refill the reservoirs while the system is still
running. After refilling the plugs should be mounted back on their
positions before the system is shut down again.
Refilling exterior loop
Refilling interior loop
Refilling the
reservoirs