background image

Application Note: Security, Alarm System 

www.topkodas.lt

  

 

11  | 

E N

   

3

16

17

4

5

6

7

14

15

18

19

12
13

9
8

10
11

20

 

Figure 18 the example of Double click on the required zone window 
 
Table 2 Explanation of every field in "Zones" window 

Zone Name 

Zone name should be entered.  

Assign Module= 

Zone Hardware Input

 

Select the zone hardware input 

Zone Disabled  

Disables the corresponding zone. 

GTalarm, IN1…IN4 

The zone hardware 

input 1… input 4 assigned 

GTalarm, I/O1… I/O2 

The zone hardware optional Input/ Output 1… Input/ Output 2 assigned 

 

Zone Definition= 

Definition

 

Delay 

When armed, provides entry delay when violated. Recommended for door sensors. 

Interior 

When armed, instant alarm will sound first if the zone is violated; instant alarm will 
follow the entry delay if entry delay is active. Recommended for motion sensor in 
front of the door.  

Instant 

When armed, instant alarm when violated. 

24 hours 

Instant alarm when violated, audible alarm at default not depending from ARM, 
DISARM modes. Recommended for safes, storehouses, tampers. 

Silent 

Always active, not depending from ARM, DISARM modes. The sms will be send, but 
the siren will not be activated. Recommended for voltage, temperature control, AC 
mains failure control and for alarm of silent panic. 

Fire 

Instant alarm and communication when violated not depending from ARM, DISARM 
modes. Siren signal with interruptions will be generated. Recommended for smoke, 
fire detectors. 

ON/OFF 

 

Interior STAY 

Similar to ‘Instant’ except the module will auto bypass the zone if Armed in the Stay 
mode 

Instant STAY 

Similar to ‘Instant’ except the module will auto -bypass the zone if Armed in the Stay 
mode 

 

Wiring Type= 

Type

 

 

EOL 

End of line resistor. Input type with resistor. 

NC 

Normal Close. The alarm will be send when the circuit between input and ground (-V) 
will be broken. 

NO 

Normal Open. The alarm will be send when the input will be connected with ground (-
V) 

 

Contact ID code= 

CID

 

The module supports Contact ID reporting. 
 If any other data is programmed the module will automatically generate the reporting event when 
transmitting to the central station. 

14 

Zone Speed= 

Speed

 

The Input Speed defines how quickly the module responds to an open zone detected on any hardwired 
input terminal (does not apply to addressable motion detectors and door contacts). 

15 

Event Repeat Timeout= 

Repeat

 

Insensitive time to recurrent zone events 

18 

Max Alarm Count=  

Alarm Limit

 

When the particular number of zone events set has occurred, the other events of the same zone will not 
be responded for the time set in Event Repeat Timeout. After this time expired (or when disarmed), a new 
count of the number of zone events will be started. 

12 

Alarm Report Enabled= 

Report A

 

The system will report alarm event and log it to the event buffer 

13 

Restore Report Enabled= 

Report R

 

The system will report restore event and log it to the event buffer 

Tamper Enabled= 

Tamper

 

The system will detect a 

tamper

 condition with one or more sensors on the system 

Bypass Enabled= 

Bypass

 

The system will allow zones to be Manually Bypassed. 

10 

Shutdown if max alarm 
count= 

Shutdown

 

The system will stop generating alarms once the 

max alarm count

 Limit is reached. It resets every time 

the system will be armed. 

11 

Zone Force ARM= 

Force

 

Only 

force

 zones can be bypassed when the module is Force armed. Fire Zones cannot be Force Zones. 

Summary of Contents for GTalarm2

Page 1: ...GTalarm2 Application Note Security Alarm System Monitoring alarm control This manual includes steps to install set up and use your system...

Page 2: ...PGM outputs 24V 1000mA Open Drain Digital expansion module BUS In field firmware upgrade via USB SERA Cloud Remote Service Events log buffer 2048 events Program remote controls using the master or ins...

Page 3: ...or to the server 1 3 First steps to prepare GTalarm2 module and Sera2 software Preparation procedure of the module GTalarm2 Connect the GSM antenna to the antenna connector Insert the SIM card in the...

Page 4: ...r supply Battery Wiring It is possible to supply the security system from stabilized power supply source 10 15 V and not less than 1 5A It is necessary to calculate max current of power supply The cur...

Page 5: ...sed or used as security system s zones with selectable type NC NO EOL EOL TAMPER 2 programmable analog inputs I O1 I O2 0 10V 0 20mA that can be used or used as security system s zone with selectable...

Page 6: ...Monitoring control via mobile phone web browser GTalarm2 Figure 5 Monitoring control via mobile phone web browser Figure 7 Monitoring via web mobile app Zone status 4 2 Monitoring via SERA2 software...

Page 7: ...Application Note Security Alarm System www topkodas lt 7 E N Figure 8 Monitoring via free Sera2 software Zone status...

Page 8: ...2012 configurable as encrypted and non encrypted Shock sensor Reporting to the central monitoring station GTalarm2 Figure 9 Reporting to the central monitoring station 4 4 Local alarm For protecting...

Page 9: ...able analog inputs I O1 I O2 0 10V 0 20mA for analog sensors control or using as security system s zone with selectable type NC NO EOL EOL TAMPER 5 1 NC NO EOL detectors wiring It is recommended to us...

Page 10: ...owing conditions If a Delay type zone is NOT violated during exit delay and a zone s with Stay attribute enabled exists the system will arm in Stay mode When arming the system in Stay mode under this...

Page 11: ...xcept the module will auto bypass the zone if Armed in the Stay mode 6 Wiring Type Type EOL End of line resistor Input type with resistor NC Normal Close The alarm will be send when the circuit betwee...

Page 12: ...ectors Figure 20 2 wire smoke detector wiring diagram o If I O1 I O2 set as 2 wire don t need connect 5 1k resistor to VD o I O1 I O2 do not have internal pull up resistors So if you want to connect N...

Page 13: ...inuous signals generated and if the alarm system is disturbed pulse signal Signal is terminated by turning off the alarm system OFF ON Flash Open Command ARM Close Alarm Open Remote Control Output des...

Page 14: ...nuous signals generated and if the alarm system is disturbed pulse signal Signal is terminated by turning off the alarm system 25 System State Output for connection of light indicator of the alarm sys...

Page 15: ...arm the system and turn OFF the alarm by dialing the system s phone number from any of 800 available user phone numbers The system ignores any incoming calls from a non listed phone number The phone c...

Page 16: ...smission Delay to enter a valid 4or 6 digits Security Code before the Central Monitoring Center CMS is notified If a valid Security Code is not entered within the 30 seconds then a message is sent to...

Page 17: ...and press Start iButton RFID programming mode to start entering iButton keys 2 Press Stop iButton programming to stop entering iButton keys 3 Write configuration by pressing Write icon C by sending SM...

Page 18: ...elow 9 2 Enter iButton keys by sending SMS message A Send SMS message to the module GTalarm2 INST123456 063 S INST Install Configuration of the parameters 123456 Installer s password Space character 0...

Page 19: ...y In order to delete the code it is necessary to enter 000000000000 7 OUT The selected input will be switched if a user will call from this number Preferred input may be assigned to each user s number...

Page 20: ...t is necessary to enter 000000000000 6 Keyb Code Key button code might be entered manually In order to delete the code it is necessary to enter 000000000000 7 OUT The selected input will be switched i...

Page 21: ...er tamper recognition 18 Tamper Disable The module will not generate an alarm or trouble 19 Trouble when disarmed alarm as per zone when armed When disarmed Generates Trouble Only The module transmits...

Page 22: ...d busy signal b The system will continue dialing the next listed user phone numbers in the priority order The system will dial again as many times as programmed and the same order as phone numbers lis...

Page 23: ...tem can be configured to report events to the monitoring station by transmitting data messages to the monitoring station The system connects to the central monitoring station when the CMS Central Moni...

Page 24: ...station to receive the connection requests TCP mode or the datagrams UDP mode transmitted by ALERT 2 Backup 1 Backup 1 central monitoring station settings 7 Transport Protocol TCP or UDP The used lin...

Page 25: ...Code Format A 4 digit or 6 digit user access code format can be selected 6 I O1 Settings 2 Wire Smoke detector Fire current loop or 0 10V Analog Input Zone or Sensor or Output or 0 20mA 4 20mA Curren...

Page 26: ...ton stops the monitoring of the module 3 IMEI IMEI number of GSM modem available in the module 4 SIM ICCID ICCID Integrated Circuit Card Identifier A SIM card contains its unique serial number ICCID I...

Page 27: ...rm shutdown for the zone is activated Allowable number of the same alarm events is reached and the same events will not be reported 6 Bypassed If checked and the color is red the zone is bypassed 7 Fo...

Page 28: ...seller with the questions about the configuration you have to Press Read icon first to read the configuration from the module the press File Save us and save the configuration Save the Events Log file...

Page 29: ...l be taken to match sensor range to room size A sensor whose range extends well beyond the boundaries of the room is acoustically hot and vulnerable to false alarms For protecting glass on more than o...

Page 30: ...icable laws codes or standards for a specific type of occupancy approved single and multiple station smoke alarms shall be installed as follows 1 In all sleeping rooms and guest rooms 2 Outside of eac...

Page 31: ...ted on the other side of closed or partly open doors If warning devices sound on a different level of the residence from the bedrooms then they are less likely to waken or alert people inside the bedr...

Reviews: