GTalarm3 User manual V-2022-05-24
34 |
E N
Start Sera2 software
Press "Connect remotely" button
Enter required parameter.
(Default App Key is 123456)
Press "Connect"
Go to Sera2> System Options> General System Options
Press "iButton/RFID/Caller ID Learning Mode"
Touch RFID keycards to the Wiegand keypad"
Press "Stop programming" button
Or wait untill the learning mode will stop automatically
Before activating the RFID learning mode
remotely, the module must have the
appropriate System Options> Digital I/O
Settings
-
For Wiegand keypad: “Wiegand interface
DATA0 and Wiegand interface DATA1
must be set.
- For iButton probe Dallas 1-Wire Bus
must be set
Refer to:
Users & Access Control programming details.
3.7
How to set clock synchronization?
If you received SMS messages with wrong date/ time, you need to set clock synchronization correctly
You can select
clock synchronization via
:
GSM modem
•
(If you will not use mobile app and cloud service)
Cloud Server
•
(If you will use mobile app)
•
SIM card must have data available
•
Insert the SIM card in your smart phone and check is the internet available
Or disable
clock synchronization
Clock synchronization via GSM modem
•
Go to SERA2> System Options> General System Options
•
Set Clock synchronization via GSM modem
•
Press “Write” in the command line
Figure 37SERA2> System Options> General System Options
Clock synchronization via Cloud server
•
Go to SERA2> GSM Communication> SERA Cloud Service
•
Enable SERA Cloud Service