GTM1 User manual V-2020-08-12
21 |
E N
How to activate output, when defined value is reached?
How to test the system: hardware status & real time sensor values, event list.
How to read event log from internal memory of the module?
How to change temperature scale from Celsius to Fahrenheit
4.2.3
Analog inputs 0-30V
If you want to edit existing configuration,
You have to read it (press “Read” in the command line)
Edit settings,
Write edited configuration (press “Write” in the command line)
Analog 0-30V sensors could be connected to IO3, IN1
Steps to start analog sensors:
Connect analog voltage sensors to IO3, IN1 according connection diagram.
If sensor connected to
IO3
, go to SERA2> System Options> General System options
Set IO3 to 0-30V Analog Input (Zone or Sensor)
Press
“Write”
in the command line
If analog inputs sensors
is not in use,
the inputs should be
disabled in “Zones” or “Sensor”
window.
Analog sensors should be calibrated and parameters should be set in the
SERA2>
Automation/Sensors
window. Go to SERA2> Automation / Sensors,
double click
on the
selected line. Sensors calibration is possible by changing multiplier, offset.
When all changes has been done, the configuration should be written to module, by pressing
write
icon.
Figure 36 SERA2> System Options> General System Options IO3 Settings> 0-30V Analog Input (Zone or Sensor)
Figure 350-30V sensor connecting diagram