26 |
E N
It is possible to set:
trigger conditions
(“Min”, “Max” and “Hys.”) and
wanted action.
SMS alarm
event values
Hysteresis
(“Hys”) is used to prevent from
excessively triggering when the value fluctuates
around the trigger point.
Example:
The wanted minimum temperature is 19°C.
So sensor1: Min=19 and Hysteresis=0.5
4.2.8
How to test the system: hardware status & real time sensor values, event list.
Real time hardware status
Go to SERA2> RT Testing & Monitoring > Hardware
Press “Start Monitoring”
Figure 41 SERA2> RT Testing & Monitoring> Hardware
Real time sensor values
Go to RT Testing & Monitoring> Sensors Automation
Figure 42 RT Testing & Monitoring> Sensors/ Automation