BTA User Guide
Topling Prnjavor
Page 19
heating system simultaneously until the temperature drops below the trigger value. When the
setting value is reached, the inlet cold cooling water and discharge apertures are close
simultaneously.
Note-As usual, the arrow on the valve body indicates the cold water supply pipe inlet
point. The valve may be installed verticaly or horizontaly, but the discharge must always be facing
downwards. It must not be install upside down. The valve should be installed at the uppermost
point of the boiler.
When pellet is used as fuel, there is a risk of overheating also.
Remedy
The boiler BTA is equipped with safety thermostat, which in case of water
temperature excess above 95
0
C, interrupt the power supply of regulator. In that case the
dosing system stops, and pellet is not enter into the boiler.
Connecting the control panel of boiler to the network
When installing the boiler, power supply cord must be connected to the boiler. The power supply
is single-phase 220 V, 50 Hz. Installation must be performed by an expert because there is a
danger of electrical shock.
Before putting into operation the work You must check:
- the pressure in the boiler and installation,
- whether complete installation is properly vented,
- whether boiler cables do not rely on the warm (hot) portions of the boiler or the cables are not
physically damaged,
- before feeding pellets into the reservoire, check that there are no mechanical hard objects that
could impede the work of the screw conveyor.
In a closed heating system the installation of a certified expansion vessel (figure 2a,
poz.7) is requred to avoid hydraulic shock. Locking element must not be installed between
the safety valve, expansion vessel and boiler. Expansion vessel is not supply with the
boiler and must be installed in the central heating system.
Water temperature in boiler may not fall below 55
0
C not to cause condansate.
In the event of severe winter weather and low temperature, and when the boiler is not used it is
necessary to drain waiter from the system or fill it with antifreeze liquid.
Summary of Contents for BTA1000
Page 70: ...BTA User Guide Topling Prnjavor Page 70...
Page 71: ...BTA User Guide Topling Prnjavor Page 71...
Page 72: ...BTA User Guide Topling Prnjavor Page 72...
Page 73: ...BTA User Guide Topling Prnjavor Page 73...
Page 74: ...BTA User Guide Topling Prnjavor Page 74...
Page 75: ...BTA User Guide Topling Prnjavor Page 75...
Page 76: ...BTA User Guide Topling Prnjavor Page 76...
Page 77: ...BTA User Guide Topling Prnjavor Page 77...
Page 78: ...BTA User Guide Topling Prnjavor Page 78...
Page 79: ...BTA User Guide Topling Prnjavor Page 79...