4 BOILER ROOM AND FUEL STORAGE
It is mandatory that individuals who have mounted the boiler or other responsible persons
related to the installation of the boiler are present during the initial commissioning. The company
carrying out the installation of the boiler is required to inform the customer with all the rules of
operation and the work of the whole system.
4. 1. Boiler room
The room in which the system is installed and where the operation is ongoing must meet
the following conditions:
- Temperature in boiler room - +5 to + 40 º C
- humidity in the room to 90% at 20 º C,
- Light in the room not less than 500 lux.
The boiler unit with its associated fittings and supporting equipment (torch, extra tank, multi-
cyclone, flue gases fan) is placed in boiler, and chimney and storage of fuel are outside the
building.Izvan facility can accommodate And the multi-cyclone in the free version. There must
have at least two safety exits in boiler room in case of fire. All approaches, such as stairs,
platforms, etc. (if any) must be secured by a fence of min. 800 mm height. Boiler room must be
so high that between the ceiling or the beams of the roof structure and the boiler is at least 1.80
m. The boiler room should be sufficiently ventilated and lighted, and the inspection of the boiler is
enabled, as well as work regarding any potential repairs and cleaning.
Fresh air for combustion must be provided in the boiler room. The boiler
room must be safe from frost, and well ventilated. If you do not follow these
instructions, a guarantee for any damages arising from any of these reasons
will be void.
Boilers over 290 kW must have two permanent and useful outputs, preferably placed
opposite each other, one of which leads directly to the outside. As such, the output can be
considered a window with metal stairs to the bottom. Boiler room door must be opened in the
direction of the exit, and doors that do not lead directly to the outside must be inflammable. The
boiler room must have at least one window looking out. Bright surface of windows should be at
least one-twelfth of the main boiler. Apparatus for opening and closing the window must be within
reach and easy to handle.
The walls, ceiling and floor of boiler room must be made of inflammable
material.
Summary of Contents for BTA1000
Page 70: ...BTA User Guide Topling Prnjavor Page 70...
Page 71: ...BTA User Guide Topling Prnjavor Page 71...
Page 72: ...BTA User Guide Topling Prnjavor Page 72...
Page 73: ...BTA User Guide Topling Prnjavor Page 73...
Page 74: ...BTA User Guide Topling Prnjavor Page 74...
Page 75: ...BTA User Guide Topling Prnjavor Page 75...
Page 76: ...BTA User Guide Topling Prnjavor Page 76...
Page 77: ...BTA User Guide Topling Prnjavor Page 77...
Page 78: ...BTA User Guide Topling Prnjavor Page 78...
Page 79: ...BTA User Guide Topling Prnjavor Page 79...