BTA User Guide
Topling Prnjavor
Page 44
Figure 19.
Selection of chimney section (Schiedel)
Figure 20.
Samples of properly set and dimensioned chimneys
In a closed heating system the installation of a certified safety valve with opening pressure of 2.5
bars is required, and installation of expansion vessel. Locking element must not be installed
between the safety valve and expansion vessel.
Water temperature in boiler may not fall below 55
0
C not to cause condensate.
In the event of severe winter weather and low temperature, and when the boiler is not used it is
necessary to drain waiter from the system or fill it with antifreeze liquid.