ON/OFF TIME SETTING INSTRUCTIONS

FOR LOADS USING NORMALLY OPEN (NO) RELAY CONTACTS

To set the INTERVAL ON time:

1. Set dial to the desired length of time that the load (fan, light, etc.) is to be turned on. The dial can be set to various positions within 

three different time ranges: 10-45 seconds, 1-45 minutes, and 1-12 hours. The dial can also be set to continuous ON and continuous 

OFF positions. 

2. The timer will begin timing the desired interval after the dial is set and the START/STOP button is pressed or after closing the external 

contacts connected to the START terminal.

3. The timing interval can be restarted by either momentarily pressing the START/STOP button or by closing the external contacts con-

nected to the start terminal.

To set for CONTINOUS ON:

Set dial and align the pointer to the ON position (approximately 12:00 o’clock position). The timer ignores any external trigger signals 

in this mode. The green ON LED will illuminate steadily when the timer is set for a continuous ON condition.

To set for CONTINOUS OFF:

Set dial to and align the pointer to the OFF position. The timer ignores any external trigger signals in this mode. The red OFF LED will 

illuminate steadily when the timer is set for a continuous OFF condition.

FOR LOADS USING NORMALLY CLOSED (NC) RELAY CONTACT:

The normally closed relay contact is provided to enable a secondary load to be switched at opposite time intervals of the main load 

(the load controlled by the normally open contact.) When the load that is connected to the normally open relay contact is ON, the load 

connected to the normally closed contact is OFF. When the load that is connected to the normally open relay contact is OFF, the load that 

is connected to the normally closed contact is ON.

PROGRAMMING & OPERATING THE TIMER

OPERATING PARAMETERS

•  The control relay will be energized continuously if the time interval dial is turned to ON and the START/STOP button is pressed or the external contacts con-

nected to the START terminal are closed. The control relay will be de-energized continuously if the time interval dial is turned to OFF. 

•  The control will repeat cycle within 1% of timing range. 

•  The control will automatically reset after a 1 second power interruption and remain OFF with the red OFF LED illuminated steadily until the START/STOP but-

ton is pressed or the external contacts connected to the START terminal are closed.

•   If the time interval dial is moved from one position to another during the active timing cycle, the timer immediately terminates the timing cycle, and the 

output is disabled. The timer must then be restarted by either pressing the START/STOP button or from external trigger contacts. A timing interval may be 

terminated by either pressing the START/STOP button or from external trigger contacts.

OnE YEar LiMitED warrantY: if this product fails because of a manufacturing defect within one year after purchase, we will, at our option, either repair or replace it at no charge. 

Our warranty does not cover damage caused by accident, abuse or misuse. we assume no further liability with respect to the sale or use of this product. tHis warrantY is in LiEu 

OF aLL OtHEr warrantiEs, EXPrEssED Or iMPLiED, inCLuDinG tHE warrantY OF MErCHantaBiLitY. we make no warranty with respect to the fitness of any goods for the 

users particular appplication. this warranty gives you specific legal rights, and you also may have other rights which vary from state to state. 

MLi-196(a)                             

NSI INDUSTRIES, LLC • 888.500.4598 • www.nsiindutries.com

Summary of Contents for E500T Series

Page 1: ...FOR TECHNICAL SUPPORT SOUTIEN TECHNIQUE PARA COMUNICARSE CON EL SERVICIO T CNICO techsupport nsiindustries com 888 500 4598...

Page 2: ...E501T ON INTERVAL TIMER INSTRUCTIONS...

Page 3: ...ing Use only mild detergent and water to dean the enclosure INSTALLATION WIRING INSTRUCTIONS Note Wiring connections are made to a six position terminal block All terminals accept AWG 18 to AWG 12 wir...

Page 4: ...ed to the normally open relay contact is OFF the load that is connected to the normally closed contact is ON PROGRAMMING OPERATING THE TIMER OPERATING PARAMETERS The control relay will be energized co...

Page 5: ...s fils de calibre AWG 18 AWG 12 1 Avant de commencer l installation coupez compl tement l alimentation du circuit de la minuterie partir du panneau de distribution 2 Des pastilles d fon ables se trouv...

Page 6: ...malement ouvert est OFF arr t celle qui est branch e sur le contact de relais normalement ferm est ON marche PROGRAMMATION ET FONCTIONNEMENT DE LA MINUTERIE PARAM TRES OP RATIONNELS Le relais de comma...

Page 7: ...ja de protecci n INSTALACI N Y CABLEADO Nota El cableado se puede conectar a un bloque de terminales de seis posiciones Todos los terminales admiten cables de AWG 18 hasta AWG 12 1 Desconecte por comp...

Page 8: ...a al contacto normalmente cerrado Cuando se desactiva la carga conectada al contacto del rel normalmente abierto se activa la carga conectada al contacto normalmente cerrado PROGRAMACI N Y FUNCIONAMIE...

Reviews: