ON/OFF TIME SETTING INSTRUCTIONS

FOR LOADS USING NORMALLY OPEN (NO) RELAY CONTACTS: 

To set the INTERVAL ON time:

1. Set dial to the desired length of time that is required to elapse before the load (fan, light, etc.) is to be turned OFF. The dial can be set 

to various positions within three different time ranges: 5-50 seconds, 1-50 minutes, and 1-3 hours. The dial can also be set to continu-

ous ON and continuous OFF positions. 

2. The timer will begin timing the desired interval after the dial is set and the external contacts connected to the START terminal are 

opened.

3. The timing interval can be restarted by closing and opening the external contacts connected to the START terminal.

To set for CONTINOUS ON:

Set dial and align the pointer to the ON position (approximately 12:00 o’clock position). The timer ignores any external trigger signals 

in this mode. The green ON LED will illuminate steadily when the timer is set for a continuous ON condition.

To set for CONTINOUS OFF:

Set dial to and align the pointer to the OFF position. The timer ignores any external trigger signals in this mode. The red OFF LED will 

illuminate steadily when the timer is set for a continuous OFF condition.

FOR LOADS USING NORMALLY CLOSED (NC) RELAY CONTACT:

The normally closed relay contact is provided to enable a secondary load to be switched at opposite time intervals of the main load (the load 

controlled by the normally open contact.) When the load that is connected to the normally open relay contact is ON, the load connected to 

the normally closed contact is OFF. When the load that is connected to the normally open relay contact is OFF, the load that is connected to 

the normally closed contact is ON.

PROGRAMMING & OPERATING THE TIMER

OPERATING PARAMETERS

•  The control relay will be energized continuously if the time interval dial is turned to ON. The control relay will be de-energized continuously if the time interval 

dial is turned to OFF. 

•  The control will repeat cycle within 1% of timing range. 

•  The control will automatically reset after a 1 second power interruption and remain OFF with the red OFF LED illuminated steadily until the external contacts 

connected to the START terminal is closed. If the external switch is closed during power failure, the load will turn ON with the green ON LED illuminated 

steadily until the external contacts are opened.

•  If the time interval dial is moved from one position to another during the active timing cycle, no change will result in the timing or output status for that cycle.

OnE YEar LiMitED warrantY: if this product fails because of a manufacturing defect within one year after purchase, we will, at our option, either repair or replace it at no charge. 

Our warranty does not cover damage caused by accident, abuse or misuse. we assume no further liability with respect to the sale or use of this product. tHis warrantY is in LiEu 

OF aLL OtHEr warrantiEs, EXPrEssED Or iMPLiED, inCLuDinG tHE warrantY OF MErCHantaBiLitY. we make no warranty with respect to the fitness of any goods for the 

users particular appplication. this warranty gives you specific legal rights, and you also may have other rights which vary from state to state. 

MLi-197(a)                             

NSI INDUSTRIES, LLC • 888.500.4598 • www.nsiindutries.com

Summary of Contents for E502T

Page 1: ...FOR TECHNICAL SUPPORT SOUTIEN TECHNIQUE PARA COMUNICARSE CON EL SERVICIO T CNICO techsupport nsiindustries com 888 500 4598...

Page 2: ...E502T OFF DELAY TIMER INSTRUCTIONS...

Page 3: ...detergent and water to dean the enclosure INSTALLATION WIRING INSTRUCTIONS Note Wiring connections are made to a six position terminal block All terminals accept AWG 18 to AWG 12 wire 1 Turn off all p...

Page 4: ...d connected to the normally closed contact is OFF When the load that is connected to the normally open relay contact is OFF the load that is connected to the normally closed contact is ON PROGRAMMING...

Page 5: ...s sont con ues pour les fils de calibre AWG 18 AWG 12 1 Avant de commencer l installation coupez compl tement l alimentation du circuit de la minuterie partir du panneau de distribution 2 Des pastille...

Page 6: ...e la charge raccord e au contact de relais normalement ouvert est OFF arr t celle qui est branch e sur le contact de relais normalement ferm est ON marche PROGRAMMATION ET FONCTIONNEMENT DE LA MINUTER...

Page 7: ...ALACI N Y CABLEADO Nota El cableado se puede conectar a un bloque de terminales de seis posicio nes Todos los terminales admiten cables de AWG 18 hasta AWG 12 1 Desconecte por completo la alimentaci n...

Page 8: ...a la carga conectada al contacto del rel normalmente abierto se desactiva la carga conectada al contacto normalmente cerrado Cuando se desactiva la carga conectada al contacto del rel normalmente abie...

Reviews: