background image

TDC+ QUICK START GUIDE 

Page 19

 / 20

 

 

CHAPTER 3: SETUP CHECK & TROUBLESHOOTING 

 

TORO 2-WIRE SETUP QUICK CHECK LIST: 

1.

 

Gateway may be connected to either front or back serial port, but you must specify which 
port you are using in central software, special data -> advanced tab.  Note that for stand-
alone Sentinel TDC (TDC+) controllers you must connect your laptop to the serial port 
on the back of the satellite, so it is best to use the front port for the connection to the 2-
wire gateway. 

2.

 

Black switch on Gateway should be set to "fiber" position.  Cable from the Sentinel to the 
Gateway should be a straight 3-wire cable provided by Toro. 

3.

 

 2-Wire / Irritrol mode should be on, Set in central software, special data-> advanced tab.  
If it was off, turn it on, and power down the Sentinel and Gateway, wait 30 seconds, and 
power back up. 

4.

 

Each station must be set up in zone data, use the Setup Toro 2-wire button on the top of 
the zone data screen to set station types and view instructions.  You will be setting station 
type, decoder address, decoder station, and daughter board number for each station.  You 
must set decoder addresses from the central, there is no way to input the alpha-characters 
from the keypad, although you can review the decoder addresses from the keypad on the 
Sentinel.  

 

CAUTION:

 It is 

highly recommended

 to use an optical isolator in the serial connection between 

the laptop and the Sentinel.   If you are not using an isolator you should always run your laptop 
on battery when connecting to the Sentinel, and don't allow any metal parts on the laptop or 
cable to come in contact with the cabinet of the Sentinel. 

 

 
IF DECODER IS NOT OPERATING: 

1.

 

After making sure all the above settings are correct, power down the Sentinel and 
Gateway, wait 30 seconds, and power back up.  The power LED on the sentinel gateway 
should be the only one on. 

2.

 

Just to the right of the Gateway's power LED is the PC Connection LED.  It should light 
and stay on the first time the Sentinel talks to the Gateway.  If this is not happening, 
check the Special data -> advanced tab setting for Toro-2 wire.  If it is correct try moving 
to the other serial port to test for a bad serial port on the Sentinel.  To make the Sentinel 
talk the Gateway, turn a decoder station on, or off and then back on. 

3.

 

The Rx and Tx LED's will light momentarily as the Sentinel is communicating, but these 
can be difficult to see in bright conditions. 

4.

 

If some decoders are working, but one is not,  double check the decoder address, decoder 
station, and daughter board numbers on zone data.  Be sure station type is set to Toro -
wire.  If this is all correct try testing decoder at gateway or use a know good decoder at 
that location. 

 

 

Summary of Contents for TDC+

Page 1: ...TORO TDC 2 WIRE STARTUP GUIDE Version 6 4 2010...

Page 2: ...OVERVIEW Your TDC Controller Interface has three main elements to use throughout the programming process These are Display Navigation Keys Keypad Programming as covered in this User s Guide will be th...

Page 3: ...or navigating in Menus Submenus and Edit Modes as well an incrementing values in programming SCHEDULE PROGRAM GROUP Key Used for selecting Program Groups or Schedules run days when programming PROGRAM...

Page 4: ...W1 to W6 Week 1 one of Schedule up to Week 6 six of Schedule SENSOR 1 Sensor Activated Switch sensor is in alternate of its Normal condition E g If Normally Open then 1 Sensor Closed O Dry contact swi...

Page 5: ...ation Rain Off Days All Manuals Off All Autos Off Station Days Off UTILITY Time Day Day Change Hour Unit Code Station Count Program Clear N O Master Two Wire Irritrol Mode ALARMS Master Minimum Unexpe...

Page 6: ...y to view or change data in the submenu IMPORTANT When entering data into one of the submenus the controller is in the Edit Mode The controller will not begin any scheduled operation until you have ex...

Page 7: ...are Satellite Programming Directory Automatic Operations Setup Irrigation Program Software Satellite Programming Directory Unsent Changes Send Changes to Satellite SETTING CONTROLLER UNIT CODE IMPORTA...

Page 8: ...eft hand side of the upper tool bar 4 In the Software Setup Window that opens click on the Database Tab 5 Select Create new database 6 Name and save your database wherever you want your database files...

Page 9: ...ust enter the same unit code s as you entered in the field You may enter a unit description location etc at this time or do it later in the process 4 Click OK once Unit Code and Description are entere...

Page 10: ...grey serial cable included with TDC Controller to Serial Comm Port on the computer and the Serial Port on the back of the TDC Control Module CAUTION It is highly recommended to use an optical isolator...

Page 11: ...communications method 4 In the Special Data Window click on the Comm Settings Tab In the Comm Settings menu you need to set up how you will communicate to the target field controller In newer version...

Page 12: ...next to these fields to initiate the upload process from the satellite 3 Upon receiving the firmware data from the satellite choose Save to continue 4 Select the Max Stations On number based on the nu...

Page 13: ...e Gateway output boards On a TDC it is recommended that you designate and utilize the front serial port because computer programming occurs through the back port 8 Choose the Advanced tab 9 Under Stat...

Page 14: ...r the Setup directory of the Navigation Tree 2 Select the Send synchronize option as Synchronize Always This option enables synchronization to occur regardless of time variation 3 Select the Log Resul...

Page 15: ...Description for each station to aid identification but it is not required 2 On the Top of Zone Data Select Setup Toro 2 Wire This sets all stations as Toro 2 Wire stations For Each Two Wire Station 3...

Page 16: ...sters with four programs assigned to each Cluster Clusters are identified as A B C and D Programs within the cluster are identified as 1 2 3 and 4 The Program window provides a separate tabbed page fo...

Page 17: ...ottom of a Program Window defined by 4 rows of 12 Slots for a total of 48 slot positions The program cycle operating sequence begins at the first Slot in row 1 and ends at the last Slot in row 4 The s...

Page 18: ...of the Water Window is automatically terminated Continuous Run Selecting Continuous Run will automatically repeat the program cycle continuously for the defined Water Window duration Activate Auxilia...

Page 19: ...es from the keypad on the Sentinel CAUTION It is highly recommended to use an optical isolator in the serial connection between the laptop and the Sentinel If you are not using an isolator you should...

Page 20: ...START GUIDE Page 20 20 MIMINUM RECOMMENDED VERSIONS Sentinel WMS Software 3 1 0 9 and later TDC Control Module Firmware Version 2 46 Checksum ba47 or Version 2 46 Checksum 22D5 Version 2 47 any Checks...

Reviews: