background image

Solving Reception Problems

The Wireless RainSensor operates under Part 15 of the FCC rules. This means that
it has to comply with certain standards and is only allowed to transmit up to a
certain power level. In rating transmitters of any form, typically a line-of-site value is
used in order to show the relative effectiveness of a transmitter and allow a trans-
mitter and receiver to be compared to one another using a fair method. The Wireless
RainSensor operates up to 300' line-of-site. This means that in an open field, with
no obstructions, the sensor module and Receiver pair will successfully communicate
up to 300' apart. However, in almost all installations, there are obstacles between
the sensor module and Receiver such as walls, floors, etc.

The obstacles will all affect the transmitted signal and typically reduce the radiated
power that will be read by the Receiver. Different objects such as walls and floors
affect the transmitted signal differently depending on the material composition,
geometry and thickness. Typically, most residential and light commercial construc-
tion materials do not reduce the effective transmitted signal enough to pose prob-
lems under normal installation conditions. However, there are some installations
with very thick, dense walls, or that involve large amounts of radio frequency inter-
ference (electrical switching rooms etc.) where the effective range of the Wireless
RainSensor may be greatly reduced.

Some helpful tips on mounting the sensor module and Receiver for the best Radio
Frequency (RF) performance:

• Always try to keep the antennas straight and fully extended (straight up on the 

Receiver and straight down on the sensor module).

• Try to maintain a parallel orientation of one antenna to the other. Avoid installing

either unit where the antennas are in close proximity to large metal objects. 

• Attempt to mount the units as close together as possible to reduce the potential

for interference or signal reduction. If the signal strength is not good in one loca-
tion, try another location - even as little as a few feet of movement can change
from a weak spot to a strong spot. Interior locations where cell phones or cord-
less phones have trouble with reception may indicate areas with poor RF signal
transmission. 

• If possible avoid an installation where the sensor module is located exactly above

the Receiver. Move the sensor module slightly offset to one side. When the RF
signal is passing through walls, keep in mind that it has less thickness to pene-
trate when it passes straight through the wall. In other words, passing diagonally
through a wall increases its effective thickness. 

9

Doc 5  12/21/04  6:36 PM  Page 9

Summary of Contents for Wireless RainSensor TWRFS

Page 1: ...ogrammed to delay the controller from resuming operation up to 4 days This feature also enables controller operation to be placed in Rain Delay mode from 1 to 5 days when inclement weather condi tions are expected Now take a moment to browse completely through this guide before starting the installation Since the Wireless RainSensors is an accessory for your irrigation controller it will be helpfu...

Page 2: ...ld 7 Water Conservation LED s Indicate the water conservation level selected 9 Adjust Button Pressed to adjust or select values within the setup and oper ating features 10 Connection Cable Multi wire cable for connection to controller Sensor Module 1 Test Spindle Pressed to manually activate the RainSensor system 2 Rain Threshold Adjustment Adjustable cap enables the rainfall threshold to be set f...

Page 3: ...roller s sensor connection terminals generally labeled SENSOR or SEN and connect the receiver wires as follows For normally open circuit Attach the WHITE and BROWN wires For normally closed circuit Attach the WHITE and YELLOW wires Note Disregard plus and minus polarity labels on the sensor terminals if present Cut or tape back the unused wire 5 Remove the valve common wire s from the terminal lab...

Page 4: ... is visible from the sensor module location Note The manual activation cycle of some controllers bypasses the sensor inputs If the Receiver is connected to the controller s sensor inputs you will need to run an automatic timed watering program for these types of controllers With the sprinklers on manually activate the sensor module by pressing and holding the test spindle The sprinklers should shu...

Page 5: ...er tighten See Figure 7A The sensor module can also be mounted on any suitable solid structure such as the side of the roof a shed or fence using the two supplied stainless steel screws See Figure 7B 2 Once securely fastened adjust the sensor module on the mounting bracket as needed to align the sensor module housing vertically 5 Rain gutter cross section view Do not over tighten thumbscrew Press ...

Page 6: ...splayed 2 Press the Adjust button to select 0 0 to 5 0 Set Temperature Threshold TWRFS models only This feature enables the temperature threshold to be set from 35 F to 45 F or 2 C to 7 C When the selected temperature is observed the sensor will signal to stop irrigation 1 Press the Setup button three times The display will indicate the current temperature threshold setting 2 Press the Adjust butt...

Page 7: ...nded period as set Using the Smart Bypass Feature Your Wireless RainSensor can be temporarily deactivated by using the built in Smart Bypass button Simply press this button once to bypass current RainSensor control The Sensor Status light will blink until the next time the sensor module dries out and automatically resets Pressing the Smart Bypass button again resumes the RainSensor control Pressin...

Page 8: ...ove the battery cover and batteries Replace using two 3V CR2032 or equiva lent batteries Install with positive side of the batteries facing up Note Properly dispose of used batteries per the battery manufacturer s recommen dations 3 Reassemble the unit in reverse order 8 CR2032 Batteries Figure 9 Doc 5 12 21 04 6 36 PM Page 8 ...

Page 9: ... installations with very thick dense walls or that involve large amounts of radio frequency inter ference electrical switching rooms etc where the effective range of the Wireless RainSensor may be greatly reduced Some helpful tips on mounting the sensor module and Receiver for the best Radio Frequency RF performance Always try to keep the antennas straight and fully extended straight up on the Rec...

Page 10: ...stallation However there is no guarantee that interference will not occur in a particular installation If this equipment does cause interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient the receiving antenna relocate the remote control rece...

Page 11: ...th adjustable rainfall sensitivity Transmitter Battery Type 2 3V cells CR2032 or equivalent Average Battery Life Five years Operating Temperature Range 20 F to 120 F Receiver Power Input 22 28 VACc VDC 100mA from existing controller timer with Class 2 UL approved transformer Relay Contacts Output Normally Open NO and Normally Closed NC 3A at 24 VAC Receiver Controls Sensor Status Indicator Signal ...

Page 12: ...U S call 951 688 9221 This warranty does not apply where equipment is used or installation is performed in any manner contrary to Toro s specifications and instructions nor where equipment is altered or modified Neither Toro nor Toro Warranty Company is liable for indirect incidental or consequential damages in connection with the use of equipment including but not limited to vegetation loss the c...

Reviews: