TOSHIBA
6 - 1
6.0
UPS Control Interface
6.1
DB25 Connector Pinout
RS-232C serial communication and Dry Contacts are both standard features available
through a DB25 female connector located on the back panel of the UPS (see Section 9.1).
The RS-232C serial communication interface allows control of the UPS from a personal
computer running special Toshiba software. The computer is connected to the UPS
through a serial RS-232C communication port. The Dry Contact interface is available as
open or closed contacts. An adapter is available from Toshiba for splitting the RS-232C
and Dry Contact interfaces into two separate DB9 connectors. Contact Toshiba for more
information on this option. The following chart shows the pin assignments for the DB25
connector.
Pin
Symbol
Description
1
0V
Supply used by Slide-In Options cards (-)
2
+9V
Supply used by Slide-In Options cards (+)
3
RXD_UPS
UPS receive line
4
TXD_UPS
UPS transmit line
5
TXD_AUX
Auxiliary transmit line
6
RXD_AUX
Auxiliary receive line
7
(not used)
8
SNMPSIG1
SNMP option card function
9
RS_Common
Common line for RS-232C communication
10
SNMPSIG2
SNMP option card function
11
DTR
UPS data terminal ready
12
DSR
UPS data set ready
13
RTS
UPS request to send
14
CTS
UPS clear to send
15
(not used)
16
Dry_Common
Common line for Dry Contact signals
17
Backup_O
Open during Battery Backup
18
Backup_C
Closed during Battery Backup
19
Low_Battery
Closed during Low Battery
20
Inverter
Closed during On-Line mode
21
Bypass
Closed during Bypass mode
22
Fault
Closed during Fault
23
(not used)
24
SD_Signal
Shutdown command signal line
25
SD_Common
Shutdown command common line
RS-232C Serial Interface
Dry Contacts
Summary of Contents for 1000 VA
Page 2: ...TOSHIBA ...