background image

11

Outdoor Unit

Installation Manual

„

Insulation of the Refrigerant Pipes

•  Insulate the refrigerant pipes for liquid and gas separately.

Heat-proof bubble polyethylene

„

Gas Leak Inspection

•  Perform a gas leak inspection for the 

fl

 are nut connections, valve stem 

connection, and service port cap without fail.

•  Use a leak detector exclusively manufactured for R32.

Flare nut connections 
(Indoor unit)

Service port cap 
connection
Valve stem cap 
connection

* Check point example (RAS-3M18U2AVG-E)

Flare nut connections 
(Outdoor unit)

„

Performing Additional Installation of an Indoor Unit

1. Collect refrigerant from the outdoor unit.
2. Turn off the circuit breaker.
3. Perform additional installation referring to the procedure from “Refrigerant 

Piping Connection” on the previous page.

7

Electrical work

WARNING

•  Be sure to comply with local regulations/ 

codes when running the wire from the 
outdoor unit to the indoor unit.

  (Size of wire and wiring method etc.)
•  A lack of electrical capacitance or 

incorrect wiring may cause an electric 
shock or a 

fi

 re.

•  To make sure that the wiring connection 

are secure, use designated cables.

•  Fix the cables securely so that no 

external force applied to the cables may 
effect the terminals.

•  If wiring connections are incomplete 

or cables are not 

fi

 xed securely, it may 

cause a 

fi

 re.

•  Be sure to ground the outdoor unit.
•  Incomplete grounding may lead to an 

electric shock.

3. Close the Handle Low of the gauge manifold valve fully, then stop 

operating the vacuum pump.
•  Leave the gauge and pump as they are for 1 or 2 minutes, then make 

sure that the compound pressure gauge reading stays at –101 kPa (–76 
cmHg).

•  You need not add refrigerant.

4. Disconnect the charge hose from the service port, then open the valve 

stem fully using a 4 mm hexagon wrench.

Hexagon wrench is 
required.

Service port cap

4 mm

Valve stem cap

5. Tighten the service valve stem cap and service port cap securely.

CAUTION

Use a torque wrench and tighten the nut at 
the speci

fi

 ed torque value.

6. Tighten all the caps on the valves securely, then perform a gas leak 

inspection.

Service valve

Tighten torque

Valve stem cap

Service port cap

Type

mm

N•m

kgf•m

N•m

kgf•m

Liquid side

6.35

14 to 18

1.4 to 1.8

Gas side

9.52

14 to 18

1.4 to 1.8

14 to 18

1.4 to 1.8

12.7

33 to 42

3.3 to 4.2

14 to 18

1.4 to 1.8

Pressure gauge

Handle Hi
(Keep full closed)

Manifold valve

Charge hose

Vacuum pump 
adapter for 
counter

fl

 ow 

preventation

Vacuum pump

Compound 

pressure gauge

–101 kPa (–76 cmHg)

Handle Low

Charge hose

Service valve at 

the liquid side

Service valve at 

the gas side

Service port 

(Valve core 

(Setting pin))

Summary of Contents for 13340

Page 1: ...oor Unit AIR CONDITIONER MULTI SPLIT TYPE Model name RAS 2M10U2AVG E RAS 2M14U2AVG E RAS 2M18U2AVG E RAS 3M18U2AVG E NOTE Descriptions about operations for the 3 indoor units in this manual are not applicable to RAS 2M10U2AVG E RAS 2M14U2AVG E and RAS 2M18U2AVG E R32 ...

Page 2: ...9 Test run 12 10 Pump down Operation 14 11 Troubleshooting 14 12 Appendix 15 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer to the Installation Manual attached to the indoor unit IMPORTANT NOTICE For details on how to install the indoor units refer to th...

Page 3: ...cates that incorrect use of this unit can result in a high possibility of severe injury 1 or death WARNING It indicates that incorrect use of this unit may cause severe injury or death CAUTION It indicates that incorrect use of this unit may cause personal injury 2 or property damage 3 1 A severe injury refers to blindness injury burns hot or cold electrical shock bone fracture or poisoning that l...

Page 4: ... WELL AS THE ADOPTION OF THIS NEW REFRIGERANT REFRIGERATING MACHINE OIL HAS ALSO BEEN CHANGED THEREFORE DURING INSTALLATION WORK BE SURE THAT WATER DUST FORMER REFRIGERANT OR REFRIGERATING MACHINE OIL DOES NOT ENTER THE REFRIGERATION CYCLE OF A NEW REFRIGERANT AIR CONDITIONER TO AVOID MIXING REFRIGERANT AND REFRIGERATING MACHINE OIL THE SIZES OF CHARGING PORT CONNECTING SECTIONS ON THE MAIN UNIT A...

Page 5: ...TING THE INDOOR UNIT AND CAUSING A FIRE HAZARD PLACE THE UNIT WELL AWAY MORE THAN 2 M FROM HEAT SOURCES SUCH AS RADIATORS HEATERS FURNACE STOVES ETC WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT R32 WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT THE GAS PRES...

Page 6: ...d the manual A dedicated circuit and the rated voltage must be used Insufficient power supply or improper installation may cause electrical shock or fire Use a cabtyre cable to connect wires in the indoor outdoor units Midway connection stranded wire and single wire connections are not allowed Improper connection or fixing may cause a fire Wiring between the indoor unit and outdoor units must be w...

Page 7: ...st or injury Do not modify the power cable connect the cable midway or use a multiple outlet extension cable Doing so may cause contact failure insulation failure or excess current resulting in fire or electrical shock If you detect any damage do not install the unit Contact your supplying dealer immediately Never modify this unit by removing any of the safety guards or bypassing any of the safety...

Page 8: ... for installation work Failure to do so may cause personal injury when handling parts with sharp edges Do not touch the air intake section or the aluminium fins of the outdoor unit It may cause injury Do not install the outdoor unit in a place which can be a nest for small animals Small animals could enter and contact internal electrical parts causing a failure or fire Request the user to keep the...

Page 9: ...s other than the above the safety protection functions may be activated Example of indoor unit class RAS B10UFV E1 is abbreviated as 10 Indoor unit class Standard connecting pipe diameter RAS 2M10U2AVG E RAS 2M14U2AVG E RAS 2M18U2AVG E RAS 3M18U2AVG E Unit C 07 or 10 or 13 6 35 9 52 mm Unit B 07 or 10 or 13 or 16 6 35 9 52 mm 6 35 9 52 mm 6 35 9 52 mm 3 6 35 9 52 mm 3 Unit A 07 or 10 or 13 or 16 6...

Page 10: ...if outdoor work is difficult you can change the procedure For example by making adjustments to the wiring and piping lengths on the inside rather than the outside When using an air conditioner under low outside temperature conditions Outside temp 5 C or lower In COOL mode prepare a duct or wind shield so that it is not affected by the wind Necessary Space for Installation If you need to install th...

Page 11: ... Do not remove the flare nuts for any ports you are not going to use for connection Do not leave the flare nut unattached for a long period of time Use a different diameter joint if the diameters of the connection port and connection piping are different Mount the different diameter joint on the connection port of the outdoor unit CAUTION KEEP IMPORTANT 6 POINTS FOR PIPING WORK 1 Take away dust an...

Page 12: ...ffect the terminals If wiring connections are incomplete or cables are not fixed securely it may cause a fire Be sure to ground the outdoor unit Incomplete grounding may lead to an electric shock 3 Close the Handle Low of the gauge manifold valve fully then stop operating the vacuum pump Leave the gauge and pump as they are for 1 or 2 minutes then make sure that the compound pressure gauge reading...

Page 13: ...for the power source and each indoor unit Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of the indoor and the outdoor unit 5 Fix the wiring connections for the power source and each indoor unit securely using a cord clamp 6 Attach the terminal cover and the valve cover Stripping Length of connecting cable for outdoor unit 55 5 5 30 1 2 3 5...

Page 14: ... or less Also there is a possibility to misjudge if the indoor temperature becomes too low by cooling operation In that case execute the cooling operation for per room and check if the connection is normal Gas Leak Inspection Refer to the Gas Leak Inspection on page 11 Test run 1 If you perform the test run in summer start running in the cooling mode first to decrease the temperature of the room t...

Page 15: ...he service valve at the liquid end 9 Make sure that the compound pressure gauge reading is 101 kPa 76 cmHg 10 Close the valve stem of the service valve at the gas end 11 The refrigerants collection operation is finished in maximum 10 minutes After the collection is finished promptly stop the operation of all the indoor unit There are cases that the compressor restarts 12 When you want to start ove...

Page 16: ...ture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel freeze ester series PVE only of ether series The winding insulation of the co...

Page 17: ......

Page 18: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1116691098 ...

Reviews: