Emergency Power Off (EPO) Connections
9.1
Shunt Trip
A shunt trip for the DC breaker on the battery cabinet is provided. This device is operated
with an applied voltage of 120VAC. When voltage is applied, the shunt trip will cause the
breaker to switch to the OFF position disabling the battery cabinet.
NOTE:
The shunt trip operates the DC Breaker of the Battery Cabinet only! The DC
breaker of the UPS remains in the ON position regardless the status of the Battery
Cabinet.
9.2
Connection diagram
NOTE:
Push button not provided.
DANGER
AC Source
(120VAC)
EPO EPO
1
2
Push Button
DC Breaker
9- 1