3 - 1
3.0
Precautions
3.1
Installation Precautions (General)
1) Install the unit in a well ventilated location; allow at least 10 cm (4 inches) on
all sides for air ventilation and for maintenance.
2) Install the unit in a stable, level, and upright position which is free of vibration.
3) Install the unit where the ambient temperature is within the correct operating
range (see Specifications Section 4.0).
4) Do not install the UPS in areas that are subject to high humidity.
5) Do not allow direct sunlight to shine on the unit.
6) Do not install the UPS in areas which are subject to contamination such as
high levels of airborne dust, metal particles, or inflammable gas.
7) Avoid installation near sources of electrical noise and always make sure that
the unit ground is intact to prevent electrical shock and to help reduce
electrical noise.
8) Do not install where water or any foreign object may get inside the UPS.
9) This UPS generates and can radiate radio-frequency energy during operation.
Although RFI noise filters are installed inside the unit there is no guarantee
that the UPS will not influence some sensitive devices which are operating
close by. If such interference is experienced, the UPS should be installed farther
away from the effected equipment and/or powered from a different source than
that of the affected equipment.
3.2
Installation Precautions (Rack mounted)
1) Install the UPS in a conventional rack-style structure. If attaching Jonathan
QD 145 slides, optional pre-tapped aluminum slide bars are available. The
optional aluminum slide bars may be attached to the sides of the unit as shown
(see detail below). The rack must be bolted to the floor,
secured
permanently to
a wall, or otherwise secured to prevent toppling.
2) Allow at least 4 inches of open space in the front of the unit for proper ventilation.
3) Allow at least 30 inches of open space at the rear of the unit for operation of
disconnect devices.
4) Use an appropriate mechanical lifting device when moving this unit into or out
of the rack structure.
CAUTION
CAUTION
Optional aluminum slide bars
(pre-tapped to accept a Jonathan
QD145 slide)
Use both handles when lifting
entire weight of the unit
Front panel cutout