Operating the UPS
5.4
Front Panel Layout
AC LINE (green lamp)
Lights
green
when normal ac input power is being supplied to the UPS
Unit.
INVERTER (green lamp)
Lights
green
when the UPS unit is operating in the run mode and the
output is normal.
FAULT (red lamp)
Lights
red
when the UPS unit has tripped in the fault mode.
OUTPUT/BATTERY (green/red lamp level meter)
The UPS unit's level meter consists of six green and two red LED lamps
5.5
UPS Inverter Mode Display
The following chart shows normal operating conditions when the UPS INVERTER
lamp is
green
.
5 - 6
Explanation
Display status
Normal
Overload
Battery
backup
Low battery
during
battery
backup
Output
All
green
lamps light and one or two
red
lamps flash
once per second.
Remove overload as quickly as
possible to prevent fault (fault timeouts vary
depending on overload condition).
When output current is between 30% and 100%, the
green
lamps light in 15% increments (from left to right)
to indicate relative output value (This sample display
shows a value level of approximately 45% to 60% of
available output current).
During battery backup all
green
and all
red
lamps
flash once per second. As the batteries discharge, the
green lamps extinguish from left to right to indicate
remaining battery capacity (This sample display shows
a value level of approximately 55% to 70% of available
battery capacity).
All green lamps are off and one or two
red
lamps
continue to flash.
UPS Run Mode Display Chart
= Flashing LED
= Steady-lit LED