External Dimensions/Panel Layout/Shipping Weights
9.4
Remote Run/Stop
Toshiba UPS models UC1A1A015C6RKP and UC1A1A020C6RKB have a Remote Run
Stop connector located on the rear panel of the UPS. This connector allows the UPS to be
switched from bypass to on-line via a remote source.
Below is a detailed view of the connector assembly.
The connector is a normally open contact and must be closed to activate.
When open, the UPS is in bypass mode.
When closed, the UPS is on-line.
Recommended external cable length should not exceed 10 meters max.
CAUTION:
To prevent malfunctions due to noise, use a shielded type cable.
The Remote Run Stop function is only available when the front panel
run switch is in the run position. Also during under voltage you can stop
but not restart.