TOSHIBA
MODEL NUMBER
UE1A1A006C6T
UE1A1A008C6T
UE1A1A010C6T
CAPACITY
600 VA (0.42 kW)
800 VA (0.56 kW)
1000 VA (0.7 kW)
Input
Input voltage
Single phase, 120 Vac, +10% to -30% (*)
Input frequency
45 to 65 Hz
Input capacity
600 VA
800 VA
1000 VA
Input power factor
Approximate unity (0.95 to 1.0)
Battery
Battery rated voltage
60 Vdc
Battery backup time when fully charged
12 min. at full load (**) 8 min. at full load (**)
7 min. at full load (**)
with 0.7 power factor at 77° F (25° C)
30 min. at half load (**) 20 min. at half load (**) 18 min. at half load (**)
Recharge time
Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)
Type of batteries
Sealed lead-acid
Output
Output voltage
Single-phase, 120 volts
Output voltage regulation
/- 3%, steady state
Output frequency(*****)
50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)
Output voltage waveform
Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Common mode
Less than 0.5V peak
Normal mode
Less than 10V peak
Rated load power factor
0.7 lagging (0.6 to 1.0)
Voltage transient characteristic
+/- 8% under 100% load step change
Rated output current (rms)
5.0A
6.7A
8.3A
Maximum output current (peak)
15.0A
20.0A
25.0A
Inverter overload capacity
150% for 30 seconds
Crest factor
3.0
Environment
Operating temperature
32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature
-4 to 104° F (-20 to 40° C)
Operating humidity
30 to 90%, no condensation
Altitude(****)
Less than 3000 ft (1000 m) above sea level
External dimensions
8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm)
Net weight
57.5 lb (26.1 kg)
57.5 lb (26.1 kg)
60.9 lb (27.6 kg)
Acoustical noise
50 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac)
83%
83%
85%
Switches
Bypass switch
Automatic bypass is provided when the run switch is in the stop
position, if a fault occurs, or if an overload occurs (transfer time is
approximately 4 msec)
Interfaces
IBM
(TM)
AS/400
LAN Manager
See section 6.0 for details.
Fault detect and input power loss
RS232 ASCII
Options
Software for unattended
computer shutdown
Contact Toshiba for details on this option
External battery pack
Contact Toshiba for details on this option
(*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
(**) Battery backup time may vary depending on the operating conditions including ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used
for battery backup.
(****) Above 3000 ft (1000 m), output capacity reduced.
(*****) Output voltage and capacity derated for 50 Hz output.