1600Xp Series installation and operation manual
Installation Precautions
NOTICE
observe the following environmental restrictions:
1.
install the unit in a well-ventilated location; allow at least 4 inches (10 cm) on all sides for air
•
ventilation and for maintenance.
Install the unit where the ambient temperature is within the range specified on
•
pages 20 and
23.
do not install the UpS in areas that are subject to high humidity.
•
do not install the UpS in areas that allow exposure to direct sunlight.
•
do not install the UpS in areas that allow exposure to high levels of airborne dust, metal
•
particles, or flammable gases.
do not install the UpS in areas near sources of electrical noise. ensuring a proper earth
•
ground
will reduce the effects of electrical noise and will reduce the potential for electrical shock.
DO NOT install the UPS in areas that would allow fluids or any foreign object to get inside the
•
UpS.
UpS is intended for permanent installation only. install the unit in a stable, level and upright position
2.
that is free of excessive vibration.
Allow at least 4 inches (100 mm) clearance on all sides of the ups
3.
for air ventilation.
Follow the instructions on the unpacking label affixed to the exterior of the UPS.
4.
WARNING
This unit contains sealed lead acid batteries
.
lack of preventative maintenance could result
in batteries exploding and emitting gasses and/or
flame. Annual preventative maintenance must be
performed by an authorized, trained technician.
WARNING
CRITICAL FUSE SIZING
incorrect fu se replacem ent size
may result in fire or inadeq uate
equ ipm ent protection.
re pla ce only with same t ype
and rating of fuse.
49455 SHEET
CAUtion/
Attention
do not disconnect
while unit is
operating
on battery power.
nes pas debrancher
sous charge.
48
52
4 SH
EE
T
risk of electric sho ck. do not re move cover.
. refer servicing to qualified se rvice personnel.
no USer SerViCeAble pArtS
inSide
to reduce the risk of fire or electric shock, install in a te mperature and
hum id ity controlled indoor area free of conduc tive conta mina nts.
en c as utilisa tion en atm osphe re controlee. Consulter la notice technique.
note: Service pe rsonnel only.
Haza rd ous live p arts inside the UpS are energized from the ba ttery supp ly
even when the input AC power is d isconnected.
Capac itors store hazard ous energ y. do not rem ove cover until 5 minutes
after d isconnecting all sources of supp ly.
battery b ackup time, which wa s factory-set at a pred etermined level,
decreases gradually b etween service period s. the ba tterie s should b e
replaced every three yea rs after the last servicing, the da te of which is
written on the id plate lo cated on the rea r side of the UpS unit, or in the
boxes b elow.
date of last ba ttery cha rge:
WARNING
CAUTION
Do not insert battery trays with the power off !
This unit is designed for hot changeable batteries!
When installing batteries, the UPS must be in the
online or bypass mode. Contact Toshiba
International Corporation for further details.
60
41
2
pn 51727
EXTERNAL BATTERY CABINET
The battery cabinet must have
a nominal battery voltage of
288VDC.
WARNING
DANGER/ATTENTION
risk of electrical shock. do n ot touch u nin su lat ed
batt ery terminals. batteries sh ould be serviced b y
qua lified service repre se ntative only. miswiring of
batt ery could result in ele ctrcal sh ock a nd/or fire.
risque de choc electrique . le circuit des ba tteries
nest pa s e so led e secteur. le s cosses des ba tteries
peu ven t prese nter une te nsion dange reu se part
rapport a la terre . Ve rifier avan t de to uch er.
DANGER
batte ry fuse is always
live. r isk of ele ctrica l
shock. Ch eck fu se
voltage an d discon nect
external batte ries
befo re cha nging fuse.
48
51
8 SH
EE
T
fig 1
fig 2
1
2
3
Unpacking instructions
p/n 48537
typeForm
oUtpUt
mFd. in U.S.A. From Foreign And domeStiC ComponentS
HoUSton, teXAS
UninterrUptible power SUpply
inpUt
SeriAl no.
pn 60381
LISTED
POWER
SUPPLY
27E5
C US
epo
14 15 16 17
ep
o
1
ep
o2
re
m
o
te
remote
1
l1
l2
g
X1
X2
208V
120V
120V
208/240V
oUtpUt
inpUt
n
X3
g
208V
USe Copper 90 CondUCtorS only. reFer to inStrUCtion mAnUAl regArding tigHtening torQUe oF terminAl bloCkS. FACtory wired For 2 08V inpUt.
Com
2
3
4
5
6
7
8
11
12
13
240V
240V
re
m
ot
e
JUmpe r Sel eCtion
5080
2
right
minimum 4 in.
(100 mm)
Clearance all
sides
Front
rear
left