13
1600Xp Series installation and operation manual
UPS
Connections
Terminal Block
the following illustration is a detail view of the terminal block and wiring connections used for 208/240
volt units (see
pages
65-66 for terminal block location).
* – if only one input line is hot, connect hot line to terminal 1 (l), and connect the neutral line to terminal 2 (n).
note 1 – if AC input power is 208 Vac rated, short terminals 11 and 12 with a jumper wire. do not jumper terminal 13 to 12 or
11. Factory Setting is 208Vac.
Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
note 2 – if AC input power is 240 Vac rated, short terminals 12 and 13 with a jumper wire. do not jumper terminal 11 to 12 or
13.
Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
240V
208/240 V
in
REMOTE1
208
EPO2
EPO1
REMOTE2
COM
240
g
X3
1
l2 (n*)
g
X1
X2
n (0V)
2
3
12
14
13
15
8
7
6
5
11
4
16 17
l1 (l*)
120 V
240 V
120 V
208 V
208V
Jumper selection
See notes 1&2
inpUt
oUtpUt