22
1600Xp Series installation and operation manual
STANDARD MODELS: 14 – 22 KVA
Capacity
14 kVA (11.9 kW)
1
18 kVA (15.3 kW)
1
22 kVA (18.7 kW)
1, 5
general
topology
true on-line
Certifications
AnSi C62.41 (ieee 587), Ul 1778, CUl, Ce, FCC Class A , neC (nFpS-70),
nemA/pe1-1993, oSHA, ASme, iSo 9001, iSo 14001:2004 , roHS Compliant
input Characteristics
input Voltage
1
Single-phase, 208/240 VAC, +10% to –30%
1
1
input Frequency
45-65 Hz (auto-sensing)
input Capacity
14 kVA
18 kVA
22 kVA
input /(max input) Current @208V
67.2 (68.9) A
86.4 (88.1) A
106 (107) A
input /(max input) Current @240V
58.2 (59.7) A
74.9 (76.3) A
92.0 (93.0) A
input power Factor
0.98 typical, 0.95 minimum@ 100% load
1
Current tHd (linear load)
< 5%
internal AC input breaker rating
100 A / 277 V
125 A / 277 V
battery Characteristics
battery type
Valve regulated lead Acid, Flame retardant
backup time, fully charged @ 0.7
power factor, 77 F
7 min.
2
5 min.
2
backup time, fully charged @ 0.85
power factor, 77 F
7 min.
2
5 min.
2
3 min.
2
recharge time
24hr. (full), 12hr.(90%) for internal batteries only
3
battery Voltage (nominal)
288 VdC
output Characteristics
output Voltage
Single-phase, 240/208/120 volts
output Voltage regulation
= ±3%
output Frequency
±0.5Hz/1.0Hz/1.5Hz (factory/authorized service center selectable only)
AUto/mAn Frequency
Factory or authorized service center selectable only
Voltage tHd
< 3% for linear load; < 6% for non-linear load
Common-mode noise
< .5 Vrms
rated load power Factor
1
0.85 (0.6 - 1.0) lagging
Efficiency (AC-DC-AC)
>86%
4
Voltage transient
< ±8% (load of 0 to 100 %)
Voltage transient recovery
50 ms to within 2% of nominal
rated output Current (rms)
58 A
75 A
91.6 A
max peak output Current
174 A
225 A
275 A
inverter overload Capacity
125%-30 sec./150%-10 sec
bypass overload Capacity
125%-10 min./1000%-1 cycle
Crest Factor
3.0
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid
1.
when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
battery
2.
backup time may vary depending on the operating conditions and ambient temperature at the installation site.
An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
3.
Subject to update without notice.
4.
derate to 18.7 kVA (15.9 kw) for 50 Hz operation.
5.