23
1600Xp Series installation and operation manual
STANDARD MODELS: 14 – 22 KVA (CONT’D)
Capacity
14 kVA (11.9 kW)
1
18 kVA (15.3 kW)
1
22 kVA (18.7 kW)
1, 4
environment
operating temperature
59 – 77 °F (15 – 25 °C)
recommended
60 Hz 32 – 104 °F (0 – 40 °C)
50 Hz 32 – 91 °F (0 – 33 °C)
Storage temperature
-4 – 104 °F (-20 – 40 °C)
installation Area
to be installed in a well ventilated area free of airborne dust,
metal particles or flammable gas, allow at least 4 inches on all sides
operating Humidity
30 – 90% (no condensation)
Altitude
< 6600 ft. (2000 m) above sea level
2
Acoustical noise
50 db (A) maximum @ 1 meter from front panel
Heat generation (typical)
6610 btU/Hr
3
8499 btU/Hr
3
10,387 btU/Hr
3
operation diagnosis
battery Check
Performed on start up, by schedule, on-demand (user configurable)
input oV protection
Standard
battery lifetime
UpS calculates battery replacement time based upon
battery ambient temperature (lCd display, led and beeps)
internal temperature
UpS gives indication of internal temperature, alarm when high temp
event data Storage
32 – operation, 32 – backup, 32 - warnings, 32 – Faults, 32 - test,
32 - System
Applications
Switches
generator compatible
bypass Switch
bypass disable
Static switch <1/4 cycle (50Hz: 5 ms/60Hz: 4.16 ms)
Automatic retransfer
Factory or authorized service center selectable only
interface/Communications
real time clock
real time Clock with backup lithium ion battery
Schedule operation
Schedule on/oFF operation of UpS using optional remoteye iii communication
software
Autostart
Automatic UpS Startup when AC is applied - option can be enabled or disabled at
user’s discretion
remote on/oFF
Standard – external terminal
led display
3 led’s indicating on-line/Fault, warning, and A/C input
operator interface
interactive touchscreen
buzzer Volume
Standard (Fixed Volume)
power Connections
Standard – Hard wire
emergency power off
Standard – terminal contacts only
remote Contacts
Standard (inV, byp, bAtt, lb, AC, Flt)
rS232 ASCii interface
toshiba UpS Communication protocol 2.0
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid
1.
when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%
2.
Subject to update without notice.
3.
derate to 18.7 kVA (15.9 kw) for 50 Hz operation.
4.