24
1600Xp Series installation and operation manual
STANDARD MODELS: 14 – 22 KVA (CONT’D)
Capacity
14 kVA (11.9 kW)
1
18 kVA (15.3 kW)
1
22 kVA (18.7 kW)
1, 2
mechanical design
enclosure
enclosure of unit made from sheet metal meeting nemA1 and Ul
Size (Hxwxd) (max)
39.0 x 17.5 x 36.1 in.
(991 x 445 x 917 mm)
paint System
powder coating
Fan panel
panel mounted on back of UpS to allow for
easy replacement of fans
battery System
battery replacement
Slide out battery packs accessible from front of UpS,
factory or authorized service center serviceable only
battery packs
designed for battery acid leakage containment with (6) batteries per pack
battery pack Size
(Hxwxd) max.
5.0 x 7.3 x 19.0 in.
(127 x 185 x 462 mm)
battery pack Quantity
8
battery manufacturer
yUASA
battery type
rew45-12Fr
toshiba part number for
battery pack
51896-FS
60995-FS
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid
1.
when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
derate to 18.7 kVA (15.9 kw) for 50 Hz operation.
2.