D5
1600XP/XPi Series Installation and Operation Manual – 60616-012
8kVA
–
UH3G2L080C61T /
H3BG2L080C61T
(Runtimes are approximate)
UPS
ESTIMATED
RUNTIME WITH ONLY INTERNAL BATTERIES @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
8
0.7
240
33.33
0.10
560
24
1
288
105
8
0.7
240
33.33
0.20
1120
24
1
288
60
8
0.7
240
33.33
0.30
1680
24
1
288
43
8
0.7
240
33.33
0.40
2240
24
1
288
30
8
0.7
240
33.33
0.50
2800
24
1
288
22
8
0.7
240
33.33
0.60
3360
24
1
288
17
8
0.7
240
33.33
0.70
3920
24
1
288
14
8
0.7
240
33.33
0.80
4480
24
1
288
12
8
0.7
240
33.33
0.90
5040
24
1
288
10
8
0.7
240
33.33
1.00
5600
24
1
288
7
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
8
0.7
240
33.33
0.10
560
24
4
288
300
8
0.7
240
33.33
0.20
1120
24
4
288
180
8
0.7
240
33.33
0.30
1680
24
4
288
150
8
0.7
240
33.33
0.40
2240
24
4
288
120
8
0.7
240
33.33
0.50
2800
24
4
288
98
8
0.7
240
33.33
0.60
3360
24
4
288
86
8
0.7
240
33.33
0.70
3920
24
4
288
72
8
0.7
240
33.33
0.80
4480
24
4
288
65
8
0.7
240
33.33
0.90
5040
24
4
288
57
8
0.7
240
33.33
1.00
5600
24
4
288
53
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 2 MATCHING BATTERY CABINETS @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
8
0.7
240
33.33
0.10
560
24
7
288
300
8
0.7
240
33.33
0.20
1120
24
7
288
300
8
0.7
240
33.33
0.30
1680
24
7
288
300
8
0.7
240
33.33
0.40
2240
24
7
288
180
8
0.7
240
33.33
0.50
2800
24
7
288
165
8
0.7
240
33.33
0.60
3360
24
7
288
135
8
0.7
240
33.33
0.70
3920
24
7
288
120
8
0.7
240
33.33
0.80
4480
24
7
288
105
8
0.7
240
33.33
0.90
5040
24
7
288
98
8
0.7
240
33.33
1.00
5600
24
7
288
90
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......