23
1600XP/XPi Series Installation and Operation Manual – 60616-012
Parameter
Description
UPS
Size
UPS
Only
UPS +
1 BC
1
UPS +
2 BC
1
526
# External Batt. Strings in Parallel
3.6 kVA
0
1
1
6 kVA
0
1
1
8-22 kVA
0
1
1
527
External Battery Capacity in A-hr
All
0
9
9
1 These settings apply to 1600XP/1600XPi Non-matching battery cabinets.
2 Battery runtimes on the UPS display will
not be accurate when using a non-Toshiba external battery
cabinet.
11.3 Starting the UPS (Normal)
Turn the main circuit breaker (MCCB) on the back of the UPS (see
Appendix A
) to the
ON
position. The
breaker should remain in the
ON
position.
Verify that the
On-Line
“12.1 Front Panel Layout” on page 24
The UPS will now be supplying power in the On-Line mode. If the On-Line LED is not illuminated push and
hold the RUN key for approximately 3 seconds.
NOTICE
When running the UPS for the first time charge the batteries for at least 24
hours (input breaker on) before operating the connected load. Failure to do so
will result in reduced battery backup time.
11.4 Stopping the UPS
To stop the UPS press and hold the
STOP
key approximately 3 seconds until the
On-Line
LED changes
from green to off (audible beep). The UPS is now in the bypass mode.
NOTICE
If the input breaker is turned off while UPS is in the bypass mode, the output
power stops. Any load devices will lose power.
Ensure that all sensitive loads have been previously shut down.
To completely stop the UPS, turn the input breaker at the back of the UPS to the
OFF
position.
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......