UPS FAULT PROTECTION FUNCTIONS (CONT’D)
Protection Item
Ambient Overheat
DC Circuit
Overvoltage
DC Circuit
Overcurrent
LCD Message
AOH
DCOV
DCOC
Cause
Fan failure;
High internal ambient
temperature
Chopper malfunction
Inverter/chopper fault
Operation Mode
After Fault
Shutdown – No output
Bypass operation – Chopper and inverter are stopped
Inverter OL – Transfer to bypass
Audible Alarm
Yes – Continuous buzzer
Visible Alarm
Red Fault LED on
Relay Contact
Alarm
Fault relay closed
Bypass relay closed
Auto-retransfer
No