1600XP/XPi Series Installation and Operation Manual – 60616-012
Unit (Capacity)
3.6kVA (3.1 kW)
1
6 kVA (5.1 kW)
1
8 kVA (6.8 kW)
1
10 kVA (8.5 kW)
1
Buzzer Volume
Standard (Fixed Volume)
Power Connections
Standard – Hard wire, Optional – Receptacle Panel w/ Power Cord
Remote Contacts
Standard (INV, BYP, BATT, LB, AC, FLT)
RS232 ASCII Interface
Toshiba UPS Communication Protocol 2.0
RemotEye 4
(Standard with XPi)
(Optional with XP)
Remote communications package (HTTP/HTTPS, SNMP, Modbus TCP/RTU, BACnet
IP/MSTP) via RJ-45 or RS-485
Mechanical Design
Topology
Unit enclosure is made from sheet metal meeting NEMA1 and UL Type 1
Size (HxWxD) (max)
22.1x 10 x 34 in.
(561 x 254 x 864
mm)
27.5 x 10 x 34 in.
(699 x 254 x 864
mm)
28.4x 13 x 34.9 in.
(721 x 330 x 886
mm)
28.4x 13 x 34.9 in.
(721 x 330 x 886
mm)
Paint System
Powder coating
Fan Panel
2
Panel mounted on back of UPS to allow for easy replacement of fans
Battery System
Battery Replacement
Slide out battery packs accessible from front of UPS. Factory or authorized service
center serviceable only.
Battery Packs
Designed for battery acid leakage containment with six (6) batteries per pack
Battery Pack Size
(HxWxD) max.
5.0 x 7.3 x 19.0 in.
(127 x 185 x 483 mm)
Battery Pack Quantity
2
3
4
Battery Manufacturer
YUASA
Battery Type
REW45-12FR
Toshiba’s Part Number for Battery
Pack
51896-FS
60995-FS
1.
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid when
the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.
Remove all sources of main AC power and wait five minutes before replacing fans.
STANDARD MODELS: 3.6 – 10 KVA (CONT’D)
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......