1600XP Series Quick Installation Guide

When operating in the inverter mode, placing the breaker in the 

OFF

 position will switch the UPS to the 

battery backup mode. The output of the UPS will continue uninterrupted to the load. The unit must be 

in the bypass mode at the time that the breaker is placed in the 

OFF

 position for the UPS to shutdown 

power to the load. 
Wait at least 5 minutes after an Emergency Power Off (EPO) before resetting the UPS breaker.  This 

allows the UPS circuitry to fully discharge. The UPS could be damaged if the unit is not fully discharged 

before the breaker is reset.

Hardwire Connections

Remove the terminal cover plate on the lower-left back side of the UPS.  Follow the directions below in wiring the unit.

Jumper Position for 208V/240V Input, 240/208/120V Output

Jumper Position for 230V Input, 230V Output

NOTE 1 – 

If AC input power is 208 Vac rated, short terminals 11 and 12 with the provided jumper wire/bus bar.  DO NOT jumper terminal 13 to 

12 or 11.  Factory Setting is 208Vac. 

Use the jumper wire/bus strip provided by Toshiba. DO NOT add any additional jumpers.

NOTE 2 – 

If AC input power is 240 Vac rated, short terminals 12 and 13 with the provided jumper wire/bus bar.  DO NOT jumper  terminal 11 to 

12 or 13.  

Use the jumper wire/bus strip provided by Toshiba. DO NOT add any additional jumpers.

NOTE 3 – 

8-22 kVA UPSs have a jumper bus bar.

Output Terminal Connections 

Connect the load to the output terminals according the load voltage requirements.  See 
the Output Terminal Voltages table to the right.

 

Wire Size and Tightening Torque

Use the following table to select the recommended wire size and terminal lug  

tightening torque for I/O wire connections.  

Item

Terminal 

Number

AWG                

3.6 kVA

AWG                

6 kVA

AWG                

8 kVA

AWG                

10 kVA

AWG            

14-18 kVA

AWG            

22 kVA

Tightening Torque  

lb.-in. (N•m)

AC Input Lines

1 and 2

1

(8)

10 

(8)

8  

(1/0)

(1/0)

(1/0)

(1/0)

14.2 (1.56)

AC Output Lines

4, 5, and 7

1

(8)

10 

(8)

8  

(1/0)

(1/0)

(1/0)

(1/0)

14.2 (1.56)

AC Output Neutral

6

1

(8)

10 

(8)

8  

(1/0)

(1/0)

(1/0)

(1/0)

14.2 (1.56)

Ground

3 and 8

1

(8)

10 

(8)

8  

(1/0)

(1/0)

(1/0)

(1/0)

14.2 (1.56)

EPO Switch

14 and 15

16

16

16

16

16

16

9.0 (0.99)

Remote Switch

16 and 17

16

16

16

16

16

16

9.0 (0.99)

Note:  Wire size presented as the recommended size followed by a bold number in () that is the maximum wire size the terminal block can 
accommodate.  See the manual, page 48, for knock-out hole sizes on the back of each model.

3

NOTICE

Output Terminal Voltages

Vout

Terminal Lugs

120 V

X3 - N, X1 - N

208 V

X3 - X2

240 V

X3 - X1

230 V

X3 - X1

Jumper 

position 

for 208 V

120 V

208/240 Vin

REMOTE1

208

EPO2

EPO1

REMOTE2

COM

240

G

X3

1

L2

G

X1

X2

N

2

3

12

14

13

15

8

7

6

5

11

4

16

17

L1

120 V

208 V

240 V

Jumper 

position 

for 240 V

230 Vin

REMOTE1

EPO2

EPO1

REMOTE2

G

X3

1

L2 (N)

G

X1

X2

N

2

3

12

14

13

15

8

7

6

5

11

4

16

17

L1 (L)

230 V

Summary of Contents for 1600XP SERIES

Page 1: ...orized to safely energize de energize ground lockout and tag circuits and equipment and clear faults 2 in accordance with established safety practices Be trained in the proper care and use of protective equipment such as safety shoes rubber gloves hard hats safety 3 glasses face shields flash clothing etc in accordance with established safety practices Be trained in rendering first aid 4 Be knowle...

Page 2: ...UPS will not influence some sensitive devices that are operating near by If such interference is experienced the UPS should be installed farther away from the affected equipment and or powered from a different source than that of the affected equipment After ensuring that all power sources are turned off and isolated in accordance with established lockout tagout procedures 10 connect the power sou...

Page 3: ...ba DO NOT add any additional jumpers Note 3 8 22 kVA UPSs have a jumper bus bar Output Terminal Connections Connect the load to the output terminals according the load voltage requirements See the Output Terminal Voltages table to the right Wire Size and Tightening Torque Use the following table to select the recommended wire size and terminal lug tightening torque for I O wire connections Item Te...

Page 4: ...r MCCB to OFF Leave the UPS off until the DC bus is safely discharged approximately 5 10 minutes Restart the UPS by switching the main circuit breaker ON The table below summarizes the initialization parameters ID Command Options 111 Rated Vin Select from 208V 230V or 240V and press Write 215 Rated Vout Select from 208V 230V or 240V and press Write 141 Input Frequency Select from 60Hz or 50Hz and ...

Reviews: