1600XP Series Single Phase Uninterruptible Power Systems 
Product Specifications – Rev 5.0 October 2013 
3.6kVA – 22kVA

 

Page 

4

 of 

9

 

 

 

4.3.3 Static Bypass Switch 

 

1)  TRANSFER  -  The  static  bypass  switch  consists  of  thyristor  switches  in  conjunction 
with  an  output  contactor  to  permit  manual  switching  from  bypass  to  UPS  and  UPS  to 
bypass without power interruption.  The UPS instantaneously transfers to bypass should 
a  component  fail  during  normal  operation  (provided  the  UPS  and  bypass  are  in 
synchronization).    Auto-retransfer  to  UPS  after  an  overload  condition  is  completed 
within one second after the bus has dropped to 100% of nominal. 

 

2) REMOTE RUN/STOP - A set of normally open dry contacts are provided to remotely 
transfer  the  UPS  on-line  and  off-line.    When  the  UPS  is  in  this  mode  of operation, the 
UPS front control panel is disabled to provide a secured configuration.  

 

 

4.3.4 Microprocessor Control System 

 

1)  DESCRIPTION - The UPS system is provided with a microprocessor internal control 
system  to  perform  start-up,  transfers,  monitoring,  and  battery  recharging.    The 
microprocessor provides information to the user (via a touch screen liquid crystal display 
with  searchable  menu  tree)  such  as  system  status,  fault  messages  and  input  and  output 
parameters. 

 

 

2)  LED INDICATORS  - The following LED indicators are provided on the UPS front 
panel displays, which mimic power flow through the UPS: 

a)

 

AC  INPUT  (Green  Lamp)  -  Lights  when  normal  AC  input  power  is  being 
supplied to the unit. 

b)

 

WARNING (Amber Lamp) – Lamp is OFF when the UPS is normal. 

c)

 

ON-LINE  FAULT  (Green/Red  Lamp)  –  GREEN  when  voltage  is  within 
specifications, and RED when voltage is out of specifications 

 
3)  SYSTEM METERING - The UPS is provided with a touch screen display which can 
display current system operation, monitor current operating mode, performance settings, 
or fault/ incident records. 

 

4)  SYSTEM  DIAGNOSTICS  -  Should  a  fault  occur  during  operation,  diagnostic 
information is displayed in the lower left corner of the touch screen. 
 

 

 

 

5) Battery Test Function 
The  UPS  is  provided  with  a  “Battery  Test”  pushbutton  to  periodically  check  the 
condition of the batteries.  Upon detection of a battery problem, the UPS shall notify the 
user of this condition allowing the user to perform a detailed check of the battery string. 
 

5.0 System Parameters 
 
 

5.1 UPS Input 

 
 

  

Input Voltage   

 

 

: 208/240VAC Single Phase 

Input Voltage Requirement 

 

: 2 Wires + Ground  

Input Voltage Variation  

 

: +10% to -30% * 

Rated Frequency 

 

 

: 50/60 Hz 

Summary of Contents for 1600XP SERIES

Page 1: ...e characteristics of insulated gate bipolar transistors IGBT to convert DC power to regulated AC power Therefore there is a constant supply of power The batteries will instantaneously supply the inverter DC power when on AC power line failure occurs 2 1 Performance Standards The UPS is designed in accordance with and is compliant with the following sections of the current revisions of the followin...

Page 2: ... The inverter converts DC power to a clean regulated AC power which feeds the load B BATTERY Upon failure of commercial AC power the UPS derives power from the battery bank and continues feeding the load with clean regulated AC power There is no interruption to the critical load upon failure or restoration of commercial AC power C RECHARGE Upon restoration of the commercial AC source the rectifier...

Page 3: ...AC power to DC which is supplied to the DC chopper From this point DC power is used to recharge the battery bank while simultaneously providing power to the inverter a Input Frequency Range 45 65 Hz continuous without battery operation b Capacity Battery recharges to within 90 of nominal from a fully discharged state in 10 times the discharge time 3 DC CHOPPER The chopper circuit consists of induc...

Page 4: ...ouch screen liquid crystal display with searchable menu tree such as system status fault messages and input and output parameters 2 LED INDICATORS The following LED indicators are provided on the UPS front panel displays which mimic power flow through the UPS a AC INPUT Green Lamp Lights when normal AC input power is being supplied to the unit b WARNING Amber Lamp Lamp is OFF when the UPS is norma...

Page 5: ...3 kW 22 kVA 18 7 kW Rated Load Power Factor 0 85 lagging Efficiency Typical 85 Minimum 83 AC AC Voltage Regulation 3 nominal balanced load Rated Frequency 50 60 Hz Autosensing or manually selectable Frequency Regulation 0 5 1 0 or 1 5 Hz Frequency Sync Range 1 0 Hz Voltage Transients 8 100 step load change 3 loss or return of input power Transient Voltage Recovery 50ms maximum to within 2 of nomin...

Page 6: ...6 0 UPS Batteries 6 1 DC Voltage Range UPS Capacity 3 6 kVA 6 kVA 8 22 kVA Nominal DC Bus Voltage 144 VDC 216 VDC 288 VDC Voltage Range 114 164 VDC 170 245 7 VDC 227 327 VDC Shutdown Voltage 114 VDC 170 VDC 227 VDC 6 2 Protection Time Internal Battery Backup provides the listed backup time at the following loads for each UPS UPS Capacity Run time at Full Load 0 7 PF 85 PF 3 6 kVA 8 min 7 min 6 kVA...

Page 7: ...creen The UPS front screen panel is TAB menu driven The touch screen has a dedicated footer that displays any alarms and faults which makes it easier for the operator just to glance over the display without having to touch the display 8 0 Dimensions Weights and Mechanical Based on Standard Models Only 8 1 UPS Enclosure The UPS is in a freestanding NEMA1 enclosure equipped with casters and leveling...

Page 8: ...ower off EPO command via its closed contact switch located on its terminal block 9 2 DB9 Dry Contacts This is a standard feature that is offered on all the 1600XP models This feature has a limited amount of status that can be monitored remotely but it stills offers the most vital alarms and faults signals The dry contacts offer the following alarms faults 1 Fault Signal 2 Normal Input Power Supply...

Page 9: ...EMD The EMD is an environmental monitoring device that provides remote monitoring of temperature humidity and other environmental conditions via standard web browser or network management systems The EMD provides automated events notification when temperature humidity or user defined dry contacts is out of configured tolerance 13 3 Matching Battery Cabinets The 1600XP can be combined with an Exter...

Reviews: