1600XP Series Single Phase Uninterruptible Power Systems 
Product Specifications – Rev 5.0 October 2013 
3.6kVA – 22kVA

 

Page 7 of 9

 

 

7.0 System Status and Control Indicators 
 

 

 

7.1  

Front Panel 

 

The UPS has a front touch screen panel that shows all of its parameters while allowing control of 
the UPS. 
 
Operation Panel Features: 
 
1)

 

AC Input Voltage green LED Indicator 

2)

 

Warning Amber LED Indicator 

3)

 

On-Line (inverter)/Fault green/red LED Indicator 

4)

 

Liquid Crystal Display (LCD) 

5)

 

UPS Control STOP (Bypass) and RUN (On-Line) from touch screen 

 
The  UPS  front  screen  panel  is  TAB menu driven. The touch  screen has a dedicated footer that 
displays  any  alarms  and  faults  which  makes  it  easier  for  the  operator  just  to  glance  over  the 
display without having to touch the display. 
 

 
8.0 Dimensions, Weights and Mechanical (Based on Standard Models Only) 
 
 

8.1 UPS Enclosure: 

 

The  UPS  is  in  a  freestanding,  NEMA1  enclosure  equipped  with  casters and leveling feet.  The 
overall dimensions and weights are as follows: 
 

 

 

 

 

1600XP 3.6kVA UPS   

 

 

 

Weight:  

 

253 lbs.  

 

 

 

Depth:   

 

34 in.   

 

 

 

Width:     

 

10 in.   

 

 

 

Height:  

 

22 in.   

 
 

 

 

 

1600XP 6kVA UPS 

 

 

 

 

Weight:  

 

354 lbs.  

 

 

 

Depth:   

 

34 in.   

 

 

 

Width:     

 

10 in.   

 

 

 

Height:  

 

28 in.   

 

 
 

 

 

 

1600XP 8kVA UPS 

 

 

 

 

Weight:  

 

466 lbs.  

 

 

 

Depth:   

 

35 in.   

 

 

 

Width:     

 

13 in.   

 

 

 

Height:  

 

28 in.   

 
 

 

 

 

1600XP 10kVA UPS 

 

 

 

 

Weight:  

 

466 lbs.  

 

 

 

Depth:   

 

35 in.   

 

 

 

Width:     

 

13 in.   

 

Summary of Contents for 1600XP SERIES

Page 1: ...e characteristics of insulated gate bipolar transistors IGBT to convert DC power to regulated AC power Therefore there is a constant supply of power The batteries will instantaneously supply the inverter DC power when on AC power line failure occurs 2 1 Performance Standards The UPS is designed in accordance with and is compliant with the following sections of the current revisions of the followin...

Page 2: ... The inverter converts DC power to a clean regulated AC power which feeds the load B BATTERY Upon failure of commercial AC power the UPS derives power from the battery bank and continues feeding the load with clean regulated AC power There is no interruption to the critical load upon failure or restoration of commercial AC power C RECHARGE Upon restoration of the commercial AC source the rectifier...

Page 3: ...AC power to DC which is supplied to the DC chopper From this point DC power is used to recharge the battery bank while simultaneously providing power to the inverter a Input Frequency Range 45 65 Hz continuous without battery operation b Capacity Battery recharges to within 90 of nominal from a fully discharged state in 10 times the discharge time 3 DC CHOPPER The chopper circuit consists of induc...

Page 4: ...ouch screen liquid crystal display with searchable menu tree such as system status fault messages and input and output parameters 2 LED INDICATORS The following LED indicators are provided on the UPS front panel displays which mimic power flow through the UPS a AC INPUT Green Lamp Lights when normal AC input power is being supplied to the unit b WARNING Amber Lamp Lamp is OFF when the UPS is norma...

Page 5: ...3 kW 22 kVA 18 7 kW Rated Load Power Factor 0 85 lagging Efficiency Typical 85 Minimum 83 AC AC Voltage Regulation 3 nominal balanced load Rated Frequency 50 60 Hz Autosensing or manually selectable Frequency Regulation 0 5 1 0 or 1 5 Hz Frequency Sync Range 1 0 Hz Voltage Transients 8 100 step load change 3 loss or return of input power Transient Voltage Recovery 50ms maximum to within 2 of nomin...

Page 6: ...6 0 UPS Batteries 6 1 DC Voltage Range UPS Capacity 3 6 kVA 6 kVA 8 22 kVA Nominal DC Bus Voltage 144 VDC 216 VDC 288 VDC Voltage Range 114 164 VDC 170 245 7 VDC 227 327 VDC Shutdown Voltage 114 VDC 170 VDC 227 VDC 6 2 Protection Time Internal Battery Backup provides the listed backup time at the following loads for each UPS UPS Capacity Run time at Full Load 0 7 PF 85 PF 3 6 kVA 8 min 7 min 6 kVA...

Page 7: ...creen The UPS front screen panel is TAB menu driven The touch screen has a dedicated footer that displays any alarms and faults which makes it easier for the operator just to glance over the display without having to touch the display 8 0 Dimensions Weights and Mechanical Based on Standard Models Only 8 1 UPS Enclosure The UPS is in a freestanding NEMA1 enclosure equipped with casters and leveling...

Page 8: ...ower off EPO command via its closed contact switch located on its terminal block 9 2 DB9 Dry Contacts This is a standard feature that is offered on all the 1600XP models This feature has a limited amount of status that can be monitored remotely but it stills offers the most vital alarms and faults signals The dry contacts offer the following alarms faults 1 Fault Signal 2 Normal Input Power Supply...

Page 9: ...EMD The EMD is an environmental monitoring device that provides remote monitoring of temperature humidity and other environmental conditions via standard web browser or network management systems The EMD provides automated events notification when temperature humidity or user defined dry contacts is out of configured tolerance 13 3 Matching Battery Cabinets The 1600XP can be combined with an Exter...

Reviews: