B-24
1600XP/XPi Series Installation and Operation Manual – 60616-012
641
Startup Delay
Timer V
alue*
Startup Delay*
R
R/W
R/W
R/W
R/W
0
(Restart Required)
Range: 0 – 800
Units: Sec
644
Remote ‘Shutdown’
Contact
State
Remote SD Status
R
R
R
R
R
0
0: Open (deactivated)
1: Closed (activated)
645
Remote ‘Shutdown’
Contact
Mode Selection
Mode of Rmt SDown
R
R/W
R/W
R/W
R/W
0: Bypass
0: Bypass state
1: Shutdown state while contact is closed. Return to
previous state when contact is open.
646
Enable LAN Shutdown
En DCntct LANSD
R
R/W
R/W
R/W
R/W
1: Enable
647
LAN Shutdown Signal
Permitted
Time Window
DCntct LANSD
Wndw
R
R/W
R/W
R/W
R/W
600
Range: 0 – 800 Units: Sec
648
Remote ‘On Batteries’
Delay
Timer
BK DContact
Delay
R
R/W
R/W
R/W
R/W
10
Delay timer between actual event occurrence and dry contact closure to signal external devices of the event.
Range: 0 – 800
Units: Sec
649
Remote ‘Low Battery’
Delay
Timer
LB DContact Delay
R
R/W
R/W
R/W
R/W
0
Delay timer between actual event occurrence and dry contact closure to signal external devices of the event.
Range: 0 – 800
Units: Sec
652
Enable Battery
Test on UPS
Startup*
En Batt
Test Sup*
R
R/W
R/W
R/W
R/W
0: Disabled
Forces a battery test when UPS starts after normal shutdown.
(Restart Required)
0: Disable
1: Enable
653
Enable
Battery T
est*
En Batt
Test*
R
R/W
R/W
R/W
R/W
1: Enabled
(Restart Required)
0: Disable
1: Enable
654
Battery
Test Condition Status
Batt T
est
Cond.
R
R
R
R
R
0
0 = Battery test prohibited because of battery test interval setup
1 = Battery test OK to perform
655
Battery T
est
Frequency
Batt T
est
Freq
R
R/W
R/W
R/W
R/W
2: Monthly
allow
0: only daily
1: only weekly
2: only monthly (Default for other values)
656
System T
emperature
Compensation
Sys. T
emp.
Comp.
-
-
-
R/W
R/w
-5
Range: -20 – 20
Units: °C
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......