D2
1600XP/XPi Series Installation and Operation Manual – 60616-012
UPS ESTIMATED RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
3.6
0.85
240
15.00
0.10
306
12
1
144
72
3.6
0.85
240
15.00
0.20
612
12
1
144
48
3.6
0.85
240
15.00
0.30
918
12
1
144
33
3.6
0.85
240
15.00
0.40
1224
12
1
144
23
3.6
0.85
240
15.00
0.50
1530
12
1
144
18
3.6
0.85
240
15.00
0.60
1836
12
1
144
14
3.6
0.85
240
15.00
0.70
2142
12
1
144
12
3.6
0.85
240
15.00
0.80
2448
12
1
144
10
3.6
0.85
240
15.00
0.90
2754
12
1
144
9
3.6
0.85
240
15.00
1.00
3060
12
1
144
7
UPS ESTIMATED RUNTIME WITH INTERNAL BATTERIES AND 1
MATCHING
BATTERY CABINET @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
3.6
0.85
240
15.00
0.10
306
12
4
144
240
3.6
0.85
240
15.00
0.20
612
12
4
144
150
3.6
0.85
240
15.00
0.30
918
12
4
144
112
3.6
0.85
240
15.00
0.40
1224
12
4
144
98
3.6
0.85
240
15.00
0.50
1530
12
4
144
82
3.6
0.85
240
15.00
0.60
1836
12
4
144
70
3.6
0.85
240
15.00
0.70
2142
12
4
144
60
3.6
0.85
240
15.00
0.80
2448
12
4
144
55
3.6
0.85
240
15.00
0.90
2754
12
4
144
50
3.6
0.85
240
15.00
1.00
3060
12
4
144
45
UPS ESTIMATED RUNTIME WITH INTERNAL BATTERIES AND 2
MATCHING
BATTERY CABINETS @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
3.6
0.85
240
15.00
0.10
306
12
7
144
300
3.6
0.85
240
15.00
0.20
612
12
7
144
240
3.6
0.85
240
15.00
0.30
918
12
7
144
180
3.6
0.85
240
15.00
0.40
1224
12
7
144
150
3.6
0.85
240
15.00
0.50
1530
12
7
144
120
3.6
0.85
240
15.00
0.60
1836
12
7
144
112
3.6
0.85
240
15.00
0.70
2142
12
7
144
98
3.6
0.85
240
15.00
0.80
2448
12
7
144
90
3.6
0.85
240
15.00
0.90
2754
12
7
144
82
3.6
0.85
240
15.00
1.00
3060
12
7
144
72
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......