D3
1600XP/XPi Series Installation and Operation Manual – 60616-012
6kVA
–
UH3G2L060C61T / H3BG2L060C61T
(Runtimes are approximate)
UPS
ESTIMATED
RUNTIME WITH ONLY INTERNAL BATTERIES @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
6
0.7
240
25.00
0.10
420
18
1
216
90
6
0.7
240
25.00
0.20
840
18
1
216
55
6
0.7
240
25.00
0.30
1260
18
1
216
40
6
0.7
240
25.00
0.40
1680
18
1
216
28
6
0.7
240
25.00
0.50
2100
18
1
216
21
6
0.7
240
25.00
0.60
2520
18
1
216
16
6
0.7
240
25.00
0.70
2940
18
1
216
14
6
0.7
240
25.00
0.80
3360
18
1
216
11
6
0.7
240
25.00
0.90
3780
18
1
216
10
6
0.7
240
25.00
1.00
4200
18
1
216
7
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
6
0.7
240
25.00
0.10
420
18
3
216
180
6
0.7
240
25.00
0.20
840
18
3
216
135
6
0.7
240
25.00
0.30
1260
18
3
216
105
6
0.7
240
25.00
0.40
1680
18
3
216
86
6
0.7
240
25.00
0.50
2100
18
3
216
70
6
0.7
240
25.00
0.60
2520
18
3
216
60
6
0.7
240
25.00
0.70
2940
18
3
216
53
6
0.7
240
25.00
0.80
3360
18
3
216
46
6
0.7
240
25.00
0.90
3780
18
3
216
43
6
0.7
240
25.00
1.00
4200
18
3
216
38
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 2 MATCHING BATTERY CABINETS @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
6
0.7
240
25.00
0.10
420
18
5
216
300
6
0.7
240
25.00
0.20
840
18
5
216
180
6
0.7
240
25.00
0.30
1260
18
5
216
150
6
0.7
240
25.00
0.40
1680
18
5
216
120
6
0.7
240
25.00
0.50
2100
18
5
216
105
6
0.7
240
25.00
0.60
2520
18
5
216
90
6
0.7
240
25.00
0.70
2940
18
5
216
82
6
0.7
240
25.00
0.80
3360
18
5
216
72
6
0.7
240
25.00
0.90
3780
18
5
216
65
6
0.7
240
25.00
1.00
4200
18
5
216
60
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......