D6
1600XP/XPi Series Installation and Operation Manual – 60616-012
UPS
ESTIMATED
RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
8
0.85
240
33.33
0.10
680
24
1
288
86
8
0.85
240
33.33
0.20
1360
24
1
288
50
8
0.85
240
33.33
0.30
2040
24
1
288
33
8
0.85
240
33.33
0.40
2720
24
1
288
23
8
0.85
240
33.33
0.50
3400
24
1
288
16
8
0.85
240
33.33
0.60
4080
24
1
288
14
8
0.85
240
33.33
0.70
4760
24
1
288
11
8
0.85
240
33.33
0.80
5440
24
1
288
9
8
0.85
240
33.33
0.90
6120
24
1
288
8
8
0.85
240
33.33
1.00
6800
24
1
288
7
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
8
0.85
240
33.33
0.10
680
24
4
288
300
8
0.85
240
33.33
0.20
1360
24
4
288
180
8
0.85
240
33.33
0.30
2040
24
4
288
120
8
0.85
240
33.33
0.40
2720
24
4
288
105
8
0.85
240
33.33
0.50
3400
24
4
288
82
8
0.85
240
33.33
0.60
4080
24
4
288
70
8
0.85
240
33.33
0.70
4760
24
4
288
60
8
0.85
240
33.33
0.80
5440
24
4
288
53
8
0.85
240
33.33
0.90
6120
24
4
288
48
8
0.85
240
33.33
1.00
6800
24
4
288
44
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 2 MATCHING BATTERY CABINETS @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
8
0.85
240
33.33
0.10
680
24
7
288
300
8
0.85
240
33.33
0.20
1360
24
7
288
300
8
0.85
240
33.33
0.30
2040
24
7
288
240
8
0.85
240
33.33
0.40
2720
24
7
288
165
8
0.85
240
33.33
0.50
3400
24
7
288
135
8
0.85
240
33.33
0.60
4080
24
7
288
120
8
0.85
240
33.33
0.70
4760
24
7
288
105
8
0.85
240
33.33
0.80
5440
24
7
288
90
8
0.85
240
33.33
0.90
6120
24
7
288
82
8
0.85
240
33.33
1.00
6800
24
7
288
72
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......