D8
1600XP/XPi Series Installation and Operation Manual – 60616-012
UPS
ESTIMATED
RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
10
0.85
240
41.67
0.10
850
24
1
288
72
10
0.85
240
41.67
0.20
1700
24
1
288
42
10
0.85
240
41.67
0.30
2550
24
1
288
25
10
0.85
240
41.67
0.40
3400
24
1
288
17
10
0.85
240
41.67
0.50
4250
24
1
288
12
10
0.85
240
41.67
0.60
5100
24
1
288
10
10
0.85
240
41.67
0.70
5950
24
1
288
9
10
0.85
240
41.67
0.80
6800
24
1
288
7
10
0.85
240
41.67
0.90
7650
24
1
288
5
10
0.85
240
41.67
1.00
8500
24
1
288
5
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
10
0.85
240
41.67
0.10
850
24
4
288
300
10
0.85
240
41.67
0.20
1700
24
4
288
150
10
0.85
240
41.67
0.30
2550
24
4
288
105
10
0.85
240
41.67
0.40
3400
24
4
288
82
10
0.85
240
41.67
0.50
4250
24
4
288
70
10
0.85
240
41.67
0.60
5100
24
4
288
57
10
0.85
240
41.67
0.70
5950
24
4
288
50
10
0.85
240
41.67
0.80
6800
24
4
288
44
10
0.85
240
41.67
0.90
7650
24
4
288
40
10
0.85
240
41.67
1.00
8500
24
4
288
35
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 2 MATCHING BATTERY CABINETS @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
10
0.85
240
41.67
0.10
850
24
7
288
300
10
0.85
240
41.67
0.20
1700
24
7
288
300
10
0.85
240
41.67
0.30
2550
24
7
288
180
10
0.85
240
41.67
0.40
3400
24
7
288
135
10
0.85
240
41.67
0.50
4250
24
7
288
112
10
0.85
240
41.67
0.60
5100
24
7
288
98
10
0.85
240
41.67
0.70
5950
24
7
288
86
10
0.85
240
41.67
0.80
6800
24
7
288
72
10
0.85
240
41.67
0.90
7650
24
7
288
65
10
0.85
240
41.67
1.00
8500
24
7
288
60
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......