D10
1600XP/XPi Series Installation and Operation Manual – 60616-012
UPS
ESTIMATED
RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
14
0.85
240
58.33
0.10
1190
24
2
288
112
14
0.85
240
58.33
0.20
2380
24
2
288
60
14
0.85
240
58.33
0.30
3570
24
2
288
43
14
0.85
240
58.33
0.40
4760
24
2
288
29
14
0.85
240
58.33
0.50
5950
24
2
288
21
14
0.85
240
58.33
0.60
7140
24
2
288
16
14
0.85
240
58.33
0.70
8330
24
2
288
13
14
0.85
240
58.33
0.80
9520
24
2
288
11
14
0.85
240
58.33
0.90
10710
24
2
288
10
14
0.85
240
58.33
1.00
11900
24
2
288
7
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
14
0.85
240
58.33
0.10
1190
24
5
288
300
14
0.85
240
58.33
0.20
2380
24
5
288
150
14
0.85
240
58.33
0.30
3570
24
5
288
98
14
0.85
240
58.33
0.40
4760
24
5
288
78
14
0.85
240
58.33
0.50
5950
24
5
288
63
14
0.85
240
58.33
0.60
7140
24
5
288
53
14
0.85
240
58.33
0.70
8330
24
5
288
45
14
0.85
240
58.33
0.80
9520
24
5
288
40
14
0.85
240
58.33
0.90
10710
24
5
288
35
14
0.85
240
58.33
1.00
11900
24
5
288
30
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 2 MATCHING BATTERY CABINETS @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
14
0.85
240
58.33
0.10
1190
24
8
288
300
14
0.85
240
58.33
0.20
2380
24
8
288
240
14
0.85
240
58.33
0.30
3570
24
8
288
150
14
0.85
240
58.33
0.40
4760
24
8
288
120
14
0.85
240
58.33
0.50
5950
24
8
288
98
14
0.85
240
58.33
0.60
7140
24
8
288
82
14
0.85
240
58.33
0.70
8330
24
8
288
72
14
0.85
240
58.33
0.80
9520
24
8
288
63
14
0.85
240
58.33
0.90
10710
24
8
288
55
14
0.85
240
58.33
1.00
11900
24
8
288
51
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......