D12
1600XP/XPi Series Installation and Operation Manual – 60616-012
UPS
ESTIMATED
RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
18
0.85
240
75.00
0.10
1530
24
2
288
90
18
0.85
240
75.00
0.20
3060
24
2
288
48
18
0.85
240
75.00
0.30
4590
24
2
288
31
18
0.85
240
75.00
0.40
6120
24
2
288
21
18
0.85
240
75.00
0.50
7650
24
2
288
16
18
0.85
240
75.00
0.60
9180
24
2
288
12
18
0.85
240
75.00
0.70
10710
24
2
288
10
18
0.85
240
75.00
0.80
12240
24
2
288
9
18
0.85
240
75.00
0.90
13770
24
2
288
7
18
0.85
240
75.00
1.00
15300
24
2
288
5
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
18
0.85
240
75.00
0.10
1530
24
5
288
240
18
0.85
240
75.00
0.20
3060
24
5
288
112
18
0.85
240
75.00
0.30
4590
24
5
288
82
18
0.85
240
75.00
0.40
6120
24
5
288
60
18
0.85
240
75.00
0.50
7650
24
5
288
50
18
0.85
240
75.00
0.60
9180
24
5
288
42
18
0.85
240
75.00
0.70
10710
24
5
288
35
18
0.85
240
75.00
0.80
12240
24
5
288
28
18
0.85
240
75.00
0.90
13770
24
5
288
24
18
0.85
240
75.00
1.00
15300
24
5
288
21
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 2 MATCHING BATTERY CABINETS @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
18
0.85
240
75.00
0.10
1530
24
8
288
300
18
0.85
240
75.00
0.20
3060
24
8
288
165
18
0.85
240
75.00
0.30
4590
24
8
288
120
18
0.85
240
75.00
0.40
6120
24
8
288
90
18
0.85
240
75.00
0.50
7650
24
8
288
78
18
0.85
240
75.00
0.60
9180
24
8
288
65
18
0.85
240
75.00
0.70
10710
24
8
288
55
18
0.85
240
75.00
0.80
12240
24
8
288
50
18
0.85
240
75.00
0.90
13770
24
8
288
45
18
0.85
240
75.00
1.00
15300
24
8
288
40
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...