D14
1600XP/XPi Series Installation and Operation Manual – 60616-012
UPS
ESTIMATED
RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
22
0.85
240
91.67
0.10
1870
24
2
288
78
22
0.85
240
91.67
0.20
3740
24
2
288
40
22
0.85
240
91.67
0.30
5610
24
2
288
23
22
0.85
240
91.67
0.40
7480
24
2
288
16
22
0.85
240
91.67
0.50
9350
24
2
288
11
22
0.85
240
91.67
0.60
11220
24
2
288
9
22
0.85
240
91.67
0.70
13090
24
2
288
7
22
0.85
240
91.67
0.80
14960
24
2
288
6
22
0.85
240
91.67
0.90
16830
24
2
288
4
22
0.85
240
91.67
1.00
18700
24
2
288
3
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
22
0.85
240
91.67
0.10
1870
24
5
288
165
22
0.85
240
91.67
0.20
3740
24
5
288
98
22
0.85
240
91.67
0.30
5610
24
5
288
65
22
0.85
240
91.67
0.40
7480
24
5
288
51
22
0.85
240
91.67
0.50
9350
24
5
288
42
22
0.85
240
91.67
0.60
11220
24
5
288
32
22
0.85
240
91.67
0.70
13090
24
5
288
26
22
0.85
240
91.67
0.80
14960
24
5
288
21
22
0.85
240
91.67
0.90
16830
24
5
288
18
22
0.85
240
91.67
1.00
18700
24
5
288
16
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 2 BATTERY MATCHING CABINETS @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
22
0.85
240
91.67
0.10
1870
24
8
288
300
22
0.85
240
91.67
0.20
3740
24
8
288
150
22
0.85
240
91.67
0.30
5610
24
8
288
105
22
0.85
240
91.67
0.40
7480
24
8
288
82
22
0.85
240
91.67
0.50
9350
24
8
288
63
22
0.85
240
91.67
0.60
11220
24
8
288
53
22
0.85
240
91.67
0.70
13090
24
8
288
46
22
0.85
240
91.67
0.80
14960
24
8
288
42
22
0.85
240
91.67
0.90
16830
24
8
288
36
22
0.85
240
91.67
1.00
18700
24
8
288
30
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......