5
1600XP/XPi Series Installation and Operation Manual – 60616-012
3. Important Safety Instructions
This manual contains important instructions that should be followed during the installation and maintenance
of the UPS and its batteries.
Hardwired UPS units are not equipped with an over-current protection device nor an output disconnect for
the AC output. Circuit breakers should be provided by the user between the UPS Input and utility power,
and the UPS output and the load input. These devices should be rated as follows:
240VAC
RATING
3.6 kVA
6 kVA
8 kVA
10 kVA
14 kVA
18 kVA
22 kVA
Input
Breaker
30 A
50 A
60 A
70 A
100 A
100 A
125 A
Output
Breaker
20 A
35 A
45 A
60 A
80 A
100 A
125 A
* Ratings are for an 80% rated device.
The nominal battery voltages for these models are as follows:
BATTERY
VOLTAGE
3.6 kVA
6 kVA
8 kVA
10 kVA
14 kVA
18 kVA
22 kVA
144 Vdc
216 Vdc
288 Vdc 288 Vdc 288 Vdc 288 Vdc 288 Vdc
Servicing of the batteries should only be performed by a qualified factory authorized representative who
is knowledgeable about batteries and the required precautions. Keep unauthorized personnel away from
batteries. To arrange for battery replacement, contact Toshiba Customer Support Center.
1.
Turn off, lockout, and tagout all equipment before connecting the power wiring to the equipment or
when performing maintenance.
2.
The
maximum ambient operating temperature is 104 °F (40 °C).
3.
Access panels should only be removed by authorized Toshiba field Service personnel.
4.
UPS servicing should be performed by qualified Toshiba representatives only.
5.
Battery servicing should be performed by qualified Toshiba representatives only.
6.
Contact your Toshiba authorized service center for battery replacement.
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......