11
1600XP/XPi Series Installation and Operation Manual – 60616-012
8. UPS Connections
8.1 Terminal Block - 208/240 V
IN
, 120/280/240 V
OUT
The following illustration is a detail view of the terminal block and wiring connections used for 208/240
volt units (see
“Appendix C: 1600XP/1600XPi Dimensions and Weights” on page C1
* – If only one input line is hot, connect hot line to terminal 1 (L), and connect the Neutral line to terminal 2 (N).
NOTE 1 – If AC input power is 208 Vac rated, short terminals 11 and 12 with a jumper wire. DO NOT jumper terminal 13 to 12 or
11. Factory Setting is 208 Vac.
Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
NOTE 2 – If AC input power is 240 Vac rated, short terminals 12 and 13 with a jumper wire. DO NOT jumper terminal 11 to 12 or
13.
Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
NOTE 3 –
EPO
and
Rmt Contacts
function – See Section 8.2
REMOTE1
208
EPO2
EPO1
REMOTE2
COM
240
G
X3
1
L2 (N*)
G
X1
X2
N (0V)
2
3
12
14
13
15
8
7
6
5
11
4
16 17
L1 (L*)
240V
208V
Jumper selection
See notes 1&2
208/240 V
in
INPUT
OUTPUT
Factory Installed N - G Jumper
1,2
Rmt Contacts
3
EPO
3
NO
NO
120 V
240 V
120 V
208 V
32 V
88 V
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......