1600XP/XPi Series Installation and Operation Manual – 60616-012
9. Product Description
An uninterruptible power system (UPS) is a system that is installed between the commercial power and the
load equipment. The UPS provides steady AC output power during commercial power short-term blackouts
or brownouts. This power is provided for a sufficient amount of time so that the load can be shut down in an
orderly fashion. This prevents loss of data and possible damage to both hardware and software.
During normal operation, the UPS uses commercial AC power. It absorbs all of the high voltage spikes and
transients caused by switching and faults, and all of the common-mode and normal mode noise which is
associated with commercial AC power. The UPS converts it all to clean DC power. From this power, the
UPS charges its batteries and generates its own extremely high quality AC waveform output. The result of
this process is maximum power conditioning and regulation.
If the AC power supplied to the UPS drops below a specified voltage level, the unit’s batteries automatically
begin supplying power instead of receiving it. This insures that the loads connected to the UPS continue
to receive power with no interruption. When AC input power becomes available again, operation returns to
normal. The unit’s batteries begin to recharge so they will be ready for the next power interruption.
9.1 Application and Use
Toshiba 1600XP/1600XPi Series of On-Line UPS provides continuous computer-grade AC power in a
compact, high performance, and energy efficient unit. The UPS unit ensures safe and reliable operation of
critical office equipment. All units feature an
audible alarm which sounds if the battery voltage drops below
a specified minimum during use. This is an additional aid to help protect valuable office data banks. All units
allow for computer interfacing.
9.2 Output Rating
Toshiba 1600XP and 1600XPi Series (208/240V) offers UPS models with the following capacities:
MODEL
Output Capacity @ 240 V Output kW @ .85PF 240 V
UH3G2L036C61T, H3BG2L036C61T
3.6 kVA
3.1 kW
UH3G2L060C61T, H3BG2L060C61T
6 kVA
5.1 kW
UH3G2L080C61T, H3BG2L080C61T
8 kVA
6.8 kW
UH3G2L100C61T, H3BG2L100C61T
10 kVA
8.5 kW
UH3G2L140C61T, H3BG2L140C61T
14 kVA
11.9 kW
UH3G2L180C61T, H3BG2L180C61T
18 kVA
15.3 kW
UH3G2L220C61T*, H3BG2L220C61T*
22 kVA*
18.7 kW*
All models are RoHS compliant with the batteries being exempt from the directive.
*NOTE: Derate to 18.7 kVA (15.9 kW) for 50 Hz operation.
9.3 Power Backup
When an electrical power failure occurs, the UPS’s internal batteries automatically supply back-up power
to the load without interruption. For example, when used to support a computer, the UPS back-up assures
enough additional time to complete the activity and store the data. This allows an orderly shutdown after a
power failure has occurred.
9.4 Power Conditioning
When commercial power is present, the UPS supplies conditioned power to the load while maintaining its
batteries in a charged condition. The UPS protects against the normal, everyday problems associated
with unreliable commercial power, including power sags, surges, signal interference, and spikes. This
protection keeps power-line problems from reaching your load, where they can cause equipment to operate
erratically, or damage software and hardware.
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......